JOHNSON CONTROLS

27

FORM 130.13-NOM8 (1021)

MODEL TCSC SIZES 07-23 

3/8” Coil Valve Package Connections

 B 

8"

203

SEE NOTE 4

10 3/4"

273

SEE NOTE 4

AIR

ON/OFF 2-WAY VALVE PACK

(LEFT HAND SHOWN)

(RIGHT HAND OPPOSITE)

SUPPLY (IN)

RETURN (OUT)

SEE NOTE 5

 A 

  4"

102

 

  12"

303

 

8 3/4"

222

SEE NOTE 4

SEE NOTE 6

 D 

9 3/4"

248

SEE NOTE 4

10 1/4"

260

SEE NOTE 4

AIR

ON/OFF 3-WAY VALVE PACK

(LEFT HAND SHOWN)

(RIGHT HAND OPPOSITE)

SUPPLY (IN)

RETURN (OUT)

SEE NOTE 5

 C 

 1 7/8"

47

 

  12"

304

 

8 3/4"

222

SEE NOTE 4

SEE NOTE 6

NOTES:

1. All dimensions are in inches [millimeters]

    All dimensions may have  1/2 [13mm]

    variation.

    Metric values are soft conversion.

2. All drawings subject to change without

    notice.

3. Consult unit selection summary

    for valve package components and

    specifications. Valve package end point

    dimensions are fixed value,regardless of

    selected valve package components.

4. Dimensions indicate space requirement

    for valve-package install. Additional

    service space requirements depend on

    option selections.

5.Valve package support structure can be

    removed.

6. SS flexible hoses are available but not

    shown.

UNIT SIZE

COIL 

ROWS

A

B

C

D

07/10

1/2/3

5-15/16" 

[151]

12-3/8" 

[314]

8-1/8" 

[206]

10" 

[254]

4

5-15/16" 

[151]

11-7/8" 

[311]

8-1/8" 

[206]

9-1/2" 

[241]

15/20/23

1/2/3

7-5/16" 

[186]

12-3/8" 

[314]

9-1/2" 

[240]

10" 

[254]

4

7-5/16" 

[186]

11-7/8" 

[311]

9-1/2" 

[240]

9-1/2" 

[241]

35/45

[TCSB & TCSQ 

ONLY]

1/2/3

7-1/16" 

[180]

12-3/8" 

[314]

9-1/4" 

[235]

10" 

[254]

4

7-1/16" 

[180]

11-7/8" 

[311]

9-1/4" 

[235]

9-1/2" 

[241]

PAGE 2 OF 3

10-80049-J

C

4/29/2021

DIMENSIONS ARE IN INCH [MM] FORMAT

+/- 1/8 [3] UNLESS OTHERWISE NOTED

DRAWING  NO

TITLE:

MODEL

 

TCSB, TCSQ & TCSC

 

3/8” DIA, HW 

COIL, VALVE PACKAGE CONNECTIONS

REV

SHEET

DATE

ALL DRAWINGS ARE SUBJECT TO CHANGE

WITHOUT PRIOR NOTICE

DO NOT SCALE DRAWING

SUBMITTAL DRAWING

THIS DRAWING CONTAINS PROPRIETARY DATA. UNAUTHORIZED DISCLOSURE,

REPRODUCTION, OR USE IS STRICTLY PROHIBITED WITHOUT WRITTEN PERMISSION.

UNCONTROLLED WHEN PRINTED

Summary of Contents for TCSC Series

Page 1: ...INSTALLATION OPERATION MAINTENANCE FAN POWERED SENSIBLE COOLING VAV TERMINALS Form 130 13 NOM8 1021 MODEL TCSC New Release...

Page 2: ...SERVICE AND CLEARANCE REQUIREMENTS 12 CHILLED WATER COIL CONNECTIONS 17 HOT WATER COIL CONNECTIONS 21 VALVE PACKAGE COIL CONNECTIONS 26 INSPECTION AND STARTUP CHECKLIST 32 MAINTENANCE 33 FACTORY PROV...

Page 3: ...age to other equipment and or environmental pollution Usually an instruction will be given together with a brief explanation NOTE is used to highlight additional information which may be helpful to yo...

Page 4: ...eaters may start automatical ly Disconnect all power and control circuits prior to servicing to avoid burns Check that rigging and lifting equip ment can safely support the equipment assembly and comp...

Page 5: ...g instructions Check for adequate ventilation so fumesdonotmigratethroughductwork to occupied spaces when welding or cutting around the equipment Do not work on damper until associ ated actuator is di...

Page 6: ...decrease to the point at which a decrease in primary air will not maintain the desired temperature the reheat will be activated to increase the discharge air temperature INSTALLATION Do not use airflo...

Page 7: ...INTO AIR VALVE INLET COLLAR When making ductwork connection to air valve inlet collar and insulating air valve inlet take caution not to damage or remove the flow sensor connections which are vital to...

Page 8: ...p 2 Remove Retaining Screws And Carefully Remove The Auxiliary Drip Pan From The Drip Pan Step 2 Visually Locate Drip Pan Retention Studs Step 1 Locate Drip Pan Retention Clip Press Upward Until Clip...

Page 9: ...tions Toxic residues and loose particles resulting from manufacturing and field piping techniques such as joint compounds soldering flux and metal shavings may be present in the unit and the piping sy...

Page 10: ...ompatibility All internal components should be checked for shipping damage and all electrical connections should be tightened to minimize problems during start up Any devices such as thermostats that...

Page 11: ...are utilized refer to the applicable Operation Manual for start up and balancing information Check that all electrical work is finished and properly terminated Check that all electrical connections a...

Page 12: ...Inches millimeters All dimensions 1 4 6mm 2 Left Hand unit shown Right Hand unit opposite 3 Standard Electrical Enclosure is integrated into unit side Includes 4 knockouts on 2 sides Provide sufficien...

Page 13: ...NAL FILTER REMOVAL SIDE ACCESS NOTES 1 All dimensions in Inches millimeters All dimensions 1 4 6mm 2 Left Hand unit shown Right Hand unit opposite 3 90 degree Electrical Enclosure is perpendicular to...

Page 14: ...OPTIONAL FILTER REMOVAL SIDE ACCESS NOTES 1 All dimensions in Inches millimeters All dimensions 1 4 6mm 2 Left Hand unit shown Right Hand unit opposite 3 Standard Electrical Enclosure is integrated in...

Page 15: ...M ACCESS OPTIONAL FILTER REMOVAL SIDE ACCESS NOTES 1 All dimensions in Inches millimeters All dimensions 1 4 6mm 2 Left Hand unit shown Right Hand unit opposite 3 90 degree Electrical Enclosure is per...

Page 16: ...ACCESS DISCHARGE END VIEW B 21 533 3 76 SIDE VIEW NOTES 1 All dimensions in Inches millimeters All dimensions 1 4 6mm 2 Left Hand unit shown Right Hand unit opposite 3 Standard Electrical Enclosure s...

Page 17: ...3 8 COILS Unit Type Coil Rows A B C 7 10 2 5 127 3 5 8 92 2 3 4 70 3 5 127 3 5 8 92 1 7 8 48 4 5 127 4 1 2 114 1 7 8 48 12 15 20 23 2 6 152 3 5 8 92 2 3 4 70 3 6 152 3 5 8 92 1 7 8 48 4 6 152 4 1 2 1...

Page 18: ...nnection Size 5 8 ODM 1 2 NOM 3 8 COILS Unit Type Coil Rows A B C 7 10 6 5 127 6 1 4 158 1 7 8 48 8 5 127 8 202 1 7 8 48 12 15 20 23 6 6 152 6 1 4 158 1 7 8 48 8 6 152 8 202 1 7 8 48 DIMENSIONS ARE IN...

Page 19: ...4 70 3 5 127 3 7 8 98 1 3 4 45 4 5 127 5 127 1 3 4 45 12 15 20 23 2 6 152 3 7 8 98 2 3 4 70 3 6 152 3 7 8 98 1 3 4 45 4 6 152 5 127 1 3 4 45 DIMENSIONS ARE IN INCH MM FORMAT DRAWING NO TITLE REV SHEE...

Page 20: ...6 5 127 7 1 8 181 1 3 4 45 8 5 127 9 1 4 235 1 3 4 45 12 15 20 23 6 6 152 7 1 8 181 1 3 4 45 8 6 152 9 1 4 235 1 3 4 45 DIMENSIONS ARE IN INCH MM FORMAT DRAWING NO TITLE REV SHEET DATE ALL DRAWINGS A...

Page 21: ...s 3 8 Coil A B C D 7 10 1 5 7 8 150 3 1 8 78 1 25 4 3 8 111 2 5 7 8 150 3 1 4 82 7 8 22 4 3 8 111 3 5 7 8 150 3 1 4 82 1 3 4 44 4 3 8 111 4 5 7 8 150 4 1 8 104 2 5 8 66 4 3 8 111 15 20 23 1 7 1 4 185...

Page 22: ...All dimensions may vary in 1 2 13mm Metric values are soft conversion 3 All drawings are subject to change without notice 4 Connection Size 5 8 ODM 1 2 NOM 5 This sheet applies to single circuit coil...

Page 23: ...COIL ONLY Unit Size Coil Rows 1 2 Coil A B C D 7 1 5 5 8 143 3 1 8 79 1 26 4 3 8 111 3 5 5 8 143 3 1 2 87 2 1 8 55 4 3 8 111 4 5 5 8 143 4 1 2 115 3 1 4 82 4 3 8 111 10 1 5 5 8 143 3 1 8 79 1 26 4 3 8...

Page 24: ...re soft conversion 3 All drawings are subject to change without notice 4 Connection Size 1 2 ODM 1 2 NOM 5 This sheet applies to single circuit coils only For multiple circuit coils refer sheet no 1 F...

Page 25: ...vary in 1 2 13mm Metric values are soft conversion 3 All drawings are subject to change without notice 4 Connection Size 5 8 ODM 1 2 NOM 5 This sheet applies to two row two circuit only For multiple...

Page 26: ...age components 4 Dimensions indicate space requirement for valve package install Additional service space requirements depend on option selections 5 Valve package support structure can be removed 6 SS...

Page 27: ...alve package components 4 Dimensions indicate space requirement for valve package install Additional service space requirements depend on option selections 5 Valve package support structure can be rem...

Page 28: ...components 4 Dimensions indicate space requirement for valve package install Additional service space requirements depend on option selections 5 Valve package support structure can be removed 6 SS fle...

Page 29: ...alve package end point dimensions are fixed value regardless of selected valve package components 4 Dimensions indicate space requirement for valve package install Additional service space requirement...

Page 30: ...ected valve package components 4 Dimensions indicate space requirement for valve package install Additional service space requirements depend on option selections 5 Valve package support structure can...

Page 31: ...d valve package components 4 Dimensions indicate space requirement for valve package install Additional service space requirements depend on option selections 5 Valve package support structure can be...

Page 32: ...late All Piping as Required Connect Supply and Return Pipe to Correct Coil Connections 4 DUCTWORK CONNECTIONS Install Ductwork Fittings Grilles as Required Proper Supply Return Grille Types Sizes Used...

Page 33: ...an one source of power may be present Discon nect lock out and tag out all power sources to avoid electrocution or shock hazards Motor Blower Assembly Fan powered terminal unit motors are equipped wit...

Page 34: ...te personal protective equipment 3 Gain access to coil either through ductwork or coil access panel HW coil only 4 Use soft brush and vacuum to remove loose debris from sides of coil 5 Straighten any...

Page 35: ...he heater back on when the elements have cooled down Should the secondary one time trip limit switch trip it will need to be replaced with a limit switch of the same rating Optional secondary manual r...

Page 36: ...ct power to unit at main panel 2 Clip switch bracket onto side of pan at low end and press firmly into place ensuring switch wires are positioned up ensure float moves freely 3 Secure bracket into sid...

Page 37: ...level reaches a point even with the electrical contacts Sensitivity may be adjusted by sliding the sensor assembly up or down along the side of the pan if necessary The sensor must be powered with 24...

Page 38: ...RV rating as that furnished from or recom mended by the factory Optional 1 and 2 pleated filters are available and can be used in this unit 1 or 2 filter clips can be purchased and will need to be use...

Page 39: ...NIT SIZE HEATING COIL FACE AREA COOLING COIL FACE AREA NOMINAL FILTER SIZES 1 THROWAWAY FACE AREA 2 THROWAWAY FACE AREA 1 PLEATED GROSS MEDIA AREA 2 PLEATED GROSS MEDIA AREA 07 0 83 0 08 2 69 0 25 1 1...

Page 40: ...n wheel Align and tighten Motor SCR set too low Readjust motor speed SCR Low Coil Capacity Incorrect airflow Check fan operating conditions Incorrect GPM Check water pumps valves and lines for obstruc...

Page 41: ...HES W G AIRFLOW CFM SIZE 0407 0410 SIZE 0507 0510 SIZE 0815 0820 0823 SIZE 1015 1020 1023 SIZE 0607 0610 0615 0620 0623 VALVE CALIBRATION CHARTS APPLICABLE CALIBRATION CHARTS ARE AFFIXED TO EACH UNIT...

Page 42: ...l Max 100 10 0 VDC High 75 8 0 VDC Med 50 6 0 VDC Low 25 4 0 VDC Low Min 13 3 0 VDC Min 6 2 5 VDC 43 10072 02 Rev A FOR REFERENCE ONLY REFER TO UNIT LABEL FOR UNIT SPECIFIC FAN CALIBRATION Max High M...

Page 43: ...5 0610 109 16 20 24 28 31 35 39 50 58 26 0615 151 19 24 30 35 40 50 60 75 85 28 0620 157 23 30 37 43 40 50 60 75 85 28 0623 159 23 30 37 43 40 50 60 75 85 28 0815 153 19 24 30 35 40 50 60 75 85 28 082...

Page 44: ...identification 1 Complete unit model number 2 Unit hand connection right or left hand while facing the direction of airflow at the inlet 3 Complete part description including any part numbers On warra...

Page 45: ...TL MAP1810 0P Quick Start Guide MAP Gateway User Guide MAP Access Portal Gateway Mobile Access Portal MAP Gateway Installation Operation and Maintenance Thermostat Wall Sensors BTN 041 141 241 Zone W...

Page 46: ...Catalog 130 13 NOM8 1021 New Release 2021 Johnson Controls P O Box 423 Milwaukee WI 53201 www johnsoncontrols com...

Reviews: