R-410A SYSTEM CHARGING PROCEDURE

Additional R-410A Charge / Orifice Size for Various Matched Systems

Outdoor Unit 

TCGF24S41S1

TCGF30S41S1

TCGF36S41S1

TCGF42S41S1

TCGF48S41S1

TCGF60S41S1

Required Orifice or TXV 

1

1TVM902

1TVM903

1TVM903

1TVM903

1TVM905

1TVM906

Factory Charge, lbs-oz

3 - 2

3 - 7

3 - 10

4 - 4

4 - 9

5 - 9

Indoor Coil

2,3,4

Additional Charge, Oz

FC/MC/PC24A3X 

 

 

 

 

 

FC/MC/PC24B3X 

 

 

 

 

 

FC/MC/PC30A3X 

12 

 

 

 

 

FC/MC/PC30B3X 

12 

 

 

 

 

FC/MC/PC32A3X 

16 

10 

 

 

 

 

FC/MC/PC35B3X 

16 

10 

 

 

 

 

FC/MC/PC35C3X 

16 

10 

 

 

 

 

FC/MC/PC36A3X 

 

 

 

 

FC/MC/PC36B3X 

 

 

 

FC/MC/PC36C3X 

 

 

 

FC/MC/PC37A3X 

24 

19 

15 

 

 

 

FC/MC/PC43B3X 

24 

19 

15 

 

 

FC/MC/PC43C3X 

24 

19 

15 

 

 

FC/MC/PC48C3X 

40 

32 

15 

17 

16 

 

FC/MC/PC48D3X 

40 

32 

27 

17 

16 

 

FC/MC/PC60D3X 

 

 

 

17 

16 

FC/MC62D3X 

 

 

 

25 

26 

18 

UC24A3X 

 

 

 

 

 

UC24B3X 

 

 

 

 

 

UC30A3X 

 

 

 

 

UC30B3X 

 

 

 

 

UC36A3X 

 

 

 

 

 

 

UC36B3X 

 

 

 

 

 

 

UC36C3X 

 

 

 

 

 

 

UC42B3X 

 

 

 

 

 

 

UC42C3X 

 

 

 

 

 

 

UC48C3X 

 

 

 

 

 

 

UC48D3X 

 

 

 

 

 

 

UC60C3X 

 

 

12 

 

 

 

UC60D3X 

 

 

12 

 

 

 

HC18A3X 

 

 

 

 

 

 

HC30A3X 

10 

 

 

 

 

 

HC36B3X 

16 

11 

 

 

 

HC42C3X 

25 

19 

15 

 

 

HC60D3X 

 

 

 

HD24*3X 

16 

 

 

 

 

 

HD36*3X 

18 

 

 

 

 

 

HD48*3X 

51 

42 

36 

24 

25 

 

HD60*3X 

 

 

 

 

24 

 

AHP18B3X 

 

 

 

 

 

 

AHP24B3X 

 

 

 

 

 

AHP30B3X 

16 

 

 

 

 

AHP36C3X 

 

19 

15 

 

 

 

Summary of Contents for TCGF24

Page 1: ...9 21 1 27 5 Locked Rotor 58 73 77 112 115 135 Crankcase Heater No No No No No No Fan Motor Amps Rated Load 8 8 1 5 1 5 1 5 1 5 Fan Diameter Inches 22 22 22 24 24 24 Fan Motor Rated HP 1 8 1 8 1 4 1 4 1 4 1 4 Nominal RPM 1075 1075 850 850 850 850 Nominal CFM 2750 2800 3200 3600 3600 3700 Coil Face Area Sq Ft 13 1 17 4 17 4 20 0 21 4 24 0 Rows Deep 1 1 1 1 1 1 Fin Inches 23 23 23 23 23 23 Liquid Lin...

Page 2: ...3X 5 FC MC PC30A3X 12 2 FC MC PC30B3X 12 2 FC MC PC32A3X 16 10 FC MC PC35B3X 16 10 FC MC PC35C3X 16 10 FC MC PC36A3X 8 4 FC MC PC36B3X 8 4 8 FC MC PC36C3X 8 4 1 FC MC PC37A3X 24 19 15 FC MC PC43B3X 24 19 15 5 FC MC PC43C3X 24 19 15 5 FC MC PC48C3X 40 32 15 17 16 FC MC PC48D3X 40 32 27 17 16 FC MC PC60D3X 17 16 0 FC MC62D3X 25 26 18 UC24A3X 8 UC24B3X 8 UC30A3X 8 4 UC30B3X 8 4 UC36A3X UC36B3X UC36C3...

Page 3: ...1 F4FV060 9 10 1 FOOTNOTES 1 Systems matched with furnace or air handlers not equipped with blower off delays may require blower Time Delay Kit 2FD06700224 2 PC coils cannot be used in downflow or horizontal applications FC coils cannot be used in horizontal applications 3 A TXV kit must be used with these coils to obtain system performance Note If a TXV is factory installed on the coil it must be...

Page 4: ...e without notice Printed in U S A 362564 UTD B 0708 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 362564 UTD A 0608 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 NOTES 362564 ...

Reviews: