Johnson Controls Unitary Products

362564-UTD-B-0708

TABULAR DATA SHEET

Outdoor Split System Air Conditioner 2 Thru 5 Tons

MODELS: TCGF24* THRU 60

14.5 SEER – R-410A, 1 PHASE

 

All dimensions are in inches. They are subject to change 
without notice. Certified dimensions will be provided upon 
request.

Physical and Electrical Data

MODEL

TCGF24S41S1

TCGF30S41S1

TCGF36S41S1

TCGF42S41S1

TCGF48S41S1

TCGF60S41S1

Unit Supply Voltage

208-230V, 1

φ,

 60Hz

Normal Voltage Range 

1

1. Rated in accordance with ARI Standard 110, utilization range “A”.

187  to 252

Minimum 

Circuit 

Ampacity

16.8 18.4 19.1 23.9 27.9 35.9 

Max. Overcurrent Device Amps 

2

2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

25 30 30 40 45 60 

Min. Overcurrent Device Amps 

3

3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

20 20 20 25 30 40 

Compressor 

Type 

Scroll Scroll Scroll Scroll Scroll Scroll 

Compressor 
Amps

Rated 

Load

12.8 14.1 14.1 17.9 21.1 27.5 

Locked 

Rotor

58 73 77 112 

115 

135 

Crankcase 

Heater

No No No No No No 

Fan Motor Amps Rated Load

.8 

.8 

1.5 

1.5 

1.5 

1.5 

Fan 

Diameter 

Inches

22 22 22 24 24 24 

Fan Motor

Rated 

HP

1/8 1/8 1/4 1/4 1/4 1/4 

Nominal 

RPM

1075 

1075 850 850 850 850 

Nominal 

CFM

2750 2800 3200 3600 3600 3700 

Coil

Face 

Area 

Sq. 

Ft.

13.1 17.4 17.4 20.0 21.4 24.0 

Rows 

Deep

1 1 1 1 1 1 

Fin 

Inches

23 23 23 23 23 23 

Liquid Line Set OD (Field Installed)

3/8 

3/8 

3/8 

3/8 

3/8 

3/8 

Vapor Line Set OD (Field Installed)

3/4 

3/4 

3/4 

7/8 

7/8 

1 1/8 

Unit Charge (Lbs. - Oz.) 

4

4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 

15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

3 - 2 

3 - 7

3 - 10 

4 - 4 

4 - 9 

5 - 9 

Charge 

Per 

Foot, 

Oz.

0.62 0.62 0.62 0.67 0.67 0.75 

Operating 

Weight 

Lbs.

128 130 145 172 180 199 

B

C

A

Unit

Model

Dimensions

(Inches)

Refrigerant Connection

Service Valve Size

A

1

1. Including Fan Guard.

B

C

Liquid

Vapor

24

28

29

29

3/8”

3/4”

30

36

29

29

36

36

29

29

42

34

33.6

33.6

7/8”

48

36

33.6

33.6

60

40

33.6

33.6

7/8”

2

2. Adapter fitting required for 1-1/8” line set.

Summary of Contents for TCGF24

Page 1: ...9 21 1 27 5 Locked Rotor 58 73 77 112 115 135 Crankcase Heater No No No No No No Fan Motor Amps Rated Load 8 8 1 5 1 5 1 5 1 5 Fan Diameter Inches 22 22 22 24 24 24 Fan Motor Rated HP 1 8 1 8 1 4 1 4 1 4 1 4 Nominal RPM 1075 1075 850 850 850 850 Nominal CFM 2750 2800 3200 3600 3600 3700 Coil Face Area Sq Ft 13 1 17 4 17 4 20 0 21 4 24 0 Rows Deep 1 1 1 1 1 1 Fin Inches 23 23 23 23 23 23 Liquid Lin...

Page 2: ...3X 5 FC MC PC30A3X 12 2 FC MC PC30B3X 12 2 FC MC PC32A3X 16 10 FC MC PC35B3X 16 10 FC MC PC35C3X 16 10 FC MC PC36A3X 8 4 FC MC PC36B3X 8 4 8 FC MC PC36C3X 8 4 1 FC MC PC37A3X 24 19 15 FC MC PC43B3X 24 19 15 5 FC MC PC43C3X 24 19 15 5 FC MC PC48C3X 40 32 15 17 16 FC MC PC48D3X 40 32 27 17 16 FC MC PC60D3X 17 16 0 FC MC62D3X 25 26 18 UC24A3X 8 UC24B3X 8 UC30A3X 8 4 UC30B3X 8 4 UC36A3X UC36B3X UC36C3...

Page 3: ...1 F4FV060 9 10 1 FOOTNOTES 1 Systems matched with furnace or air handlers not equipped with blower off delays may require blower Time Delay Kit 2FD06700224 2 PC coils cannot be used in downflow or horizontal applications FC coils cannot be used in horizontal applications 3 A TXV kit must be used with these coils to obtain system performance Note If a TXV is factory installed on the coil it must be...

Page 4: ...e without notice Printed in U S A 362564 UTD B 0708 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 362564 UTD A 0608 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 NOTES 362564 ...

Reviews: