T9800 series BACnet MS/TP Networked Thermostat Controller Technical Bulletin
Rev 1.4
9 |
P a g e
KEY-LOCK
No Lockout
Level 1 ->Lock all
keys
Level 2 ->Lock the
keys except Fan
Speed and Temp
Adjustment keys
Level 3 ->Lock the
ON/OFF and Clock
keys
Level 4 ->Lock the
keys except
ON/OFF key
MV-1322
ALWAYS
ALWAYS
ALWAYS
TEMP-DISP
Room Temperature
Setpoint
humidity
MV-1324
ALWAYS
ALWAYS
ALWAYS
4.2 Points descriptions
T9800
The T9800 device object.
L-ZNT
Internal temperature sensor.
L-ZNH
Internal humidity sensor.
R-ZNT
Remote temperature sensor.
AI-1
0~10VDC input.
AO-1
AO object to control the modulation valve.
AO-2
AO object to control the modulation valve.
BI-STATUS
Hardware binary input.
RLY-1
BO object to control the valve.
RLY-2
BO object to control the valve.
RLY-3
BO object to control the valve.
RLY-4
BO object to control the valve.
RLY-5