04: lock the keys except on/off
4
T7000
Item
T7600-
TF21-
...JS0
T7601-
TF20-
...JS0
T7600-
TF20-
...JS0
T7603-
T000-
...JF0
T7600-
TB21-
...JA0
Parameter
Function
Default
11
■
ECM Max voltage
Max voltage above which the fan output is 100%, range 0-10V.
10V
12
■
ECM cut off relay
00: Disabled; 01: Enabled
00
13
■
■
■
■
■
Restart after power failure
00: keep last status; 01: on; 02: off
00
14
■
■
■
■
■
Keypad lock
00: no lock;
01: lock all keys;
02: lock the keys except fan speed and temp. adjustment;
03: lock on/off and general;
00
15
■
■
■
■
■
Default display
00: display room temp.; 01: display set point only
00
16
■
■
■
■
Auto changeover
00: disable; 01: enable (When 2 pipe requires 10K NTC on water tube) 00
17
■
■
■
■
■
Digital input function
00: open indicates key card is inserted (occupied), closed indicates key
card is pulled out (unoccupied);
01: closed indicates key card is inserted (occupied), open indicates key
card is pulled out (unoccupied);
02: closed indicates dew point risk, open indicates no dew point risk;
03: open indicates dew point risk, closed indi-cates no dew point risk;
04: open indicates occupied, closed indicates unoccupied, shut off fan
and valve;
05: closed indicates filter alarm; 06: open indicates filter alarm
00
18
■
■
■
■
■
Unit selection
00: Celsius degree (
℃
); 01: Fahrenheit degree (
o
F)
00
19
■
■
■
■
■
Temperature offset
Setting range –5~5
℃
(-9~9
o
F)
0
20
■
■
■
■
Fan speed
00: 3 speed;
01: 2 speed (wiring MED, LOW);
02: 1 speed (wiring LOW);
03: no fan
00
21
■
■
■
■
■
Language
00: Chinese; 01: English
00
22
■
■
■
■
Mode selection
00: cooling/heating/ventilation; 01: cooling only; 02: heating
00
23
■
■
■
■
■
Back light
The back light will be OFF in 05 ... 60 Sec
30
25
■
■
■
■
■
Remote sensor type
00: China market 10KNTC; 01: JCI type II 10kNTC
00
26
■
■
■
■
■
MODBUS address
1-64
1
27
■
■
■
■
■
Baud rate
00: 9600; 01: 4800
00
28
■
■
■
Sample time
Setting range 1~99s
10
29
■
■
■
■
■
Deadband
Setting range 0~10
℃
1
30
■
■
■
KP
Setting range 1~99
10
31
■
■
■
KI
Setting range 0~99
01
32
■
■
TiO2/ESP operation
00: operate separately (corresponding button); 01: work with FCU fan
00
33
■
■
Inter stage difference
Setting range 0~10
℃
3
34
■
■
Heating stage
00: 2 stage; 01: 1 stage
00
• Terminal blocks represent the most common application. Please check the application table first
•
The r
elay output are line voltage, they are connected with line voltage internally inside thermostat
•
The OC
C terminal can assume different meaning depending on parameter 17 setting
• The functionality of the remote NTC is depending by P25 and P16 parameters
Alarm Code Description
Item
Code
Description
1
E1
Internal sensor shorted warning
2
E2
Internal sensor opened warning
3
HI
High temperature warning. Room Temperature > 55
℃
4
LO
Low temperature warning. Room Temperature < 0
℃
5
E3
Remote sensor shorted
6
E4
Remote sensor opened
7
E5
Dew point risk warning
· E3,E4 only available for 2-pipe, auto mode enabled.
· icon will twinkle if there is filter alarm
·
COM
symbol will flash if there are communication fault
· If the remote sensor is enabled, the E1/E2 warning will be ignored. If E1/E2 warning happened, T7000 will shut off the fan and close the valve.