Table 4: Changeover bypass wiring diagram
Number Description
Object name (if
given)
1
Economizer Damper Output (optional)
MAD-O
2
Supply fan output (to fan VFD)
SF-O
3
Supply fan command (to fan VFD)
SF-C
4
Heating stage 1 command
HTG1-C
5
Heating stage 2 command
HTG2-C
6
Cooling stage 1 command
CLG1-C
7
Cooling stage 2 command
CLG2-C
8
Cooling stage 3 command
CLG3-C
9
Cooling stage 4 command
CLG4-C
10
24 V HOT to damper motor
n/a
11
24 V COM to damper motor
n/a
12
24 V COM
n/a
13
24 V HOT
n/a
14
From last device
n/a
15
To next device
n/a
16
Zone humidity sensor - monitor only (optional)
ZN-H
Table 4: Changeover bypass wiring diagram
Number Description
Object name (if
given)
17
Return air CO
2
Range: 0 ppm to 2,000 ppm, 0 VDC to 10 VDC
RA-CO2
18
Return air temperature sensor
RA-T
19
Outside air temperature sensor
Note:
This is a required sensor if the VEC100
controls the economizer. Position the sensor
in a shaded area on the north side of the
building.
OA-T
20
Discharge air static pressure sensor
Range: 0 in. W.C. to 5 in. W.C., 0 VDC to 5 VDC
DA-P
21
Discharge air temperature sensor
DA-T
22
Supply fan status (air proving switch, optional)
SF-S
23
Purge input (optional)
PURGE-S
24
Filter status (optional)
FILTER-S
VEC100 Generic RTU Controller, Staged Heating and Staged Cooling Quick Start Guide