background image

Table 4: Changeover bypass wiring diagram

Number Description

Object name (if
given)

1

Economizer Damper Output (optional)

MAD-O

2

Supply fan output (to fan VFD)

SF-O

3

Supply fan command (to fan VFD)

SF-C

4

Heating stage 1 command

HTG1-C

5

Heating stage 2 command

HTG2-C

6

Cooling stage 1 command

CLG1-C

7

Cooling stage 2 command

CLG2-C

8

Cooling stage 3 command

CLG3-C

9

Cooling stage 4 command

CLG4-C

10

24 V HOT to damper motor

n/a

11

24 V COM to damper motor

n/a

12

24 V COM

n/a

13

24 V HOT

n/a

14

From last device

n/a

15

To next device

n/a

16

Zone humidity sensor - monitor only (optional)

ZN-H

Table 4: Changeover bypass wiring diagram

Number Description

Object name (if
given)

17

Return air CO

2

Range: 0 ppm to 2,000 ppm, 0 VDC to 10 VDC

RA-CO2

18

Return air temperature sensor

RA-T

19

Outside air temperature sensor

Note: 

This is a required sensor if the VEC100

controls the economizer. Position the sensor

in a shaded area on the north side of the

building.

OA-T

20

Discharge air static pressure sensor

Range: 0 in. W.C. to 5 in. W.C., 0 VDC to 5 VDC

DA-P

21

Discharge air temperature sensor

DA-T

22

Supply fan status (air proving switch, optional)

SF-S

23

Purge input (optional)

PURGE-S

24

Filter status (optional)

FILTER-S

VEC100 Generic RTU Controller, Staged Heating and Staged Cooling Quick Start Guide

5

Summary of Contents for SMART EQUIPMENT VERASYS VEC100

Page 1: ...tus device State 1 duct static pressure sensor State 2 none Rooftop Controller Type State 0 changeover bypass State 1 VAV Cancel ASCD Timers State 0 false State 1 true Demand Ventilation Feature State 0 demand ventilation is off State 1 demand ventilation is on Mounting the controller To mount the controller complete the following steps 1 Mount a 20 cm 8 in section of 35 mm 1 3 in DIN rail horizon...

Page 2: ...ply power terminal block The 24 VAC supply power terminal block is a gray removable 3 terminal plug that fits into a board mounted jack on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in the following figure The middle terminal on the supply power terminal block is not used Figure 5 24 VAC Supply ...

Page 3: ... your credentials 2 Navigate to Product Information Support Device Updates 3 Download the package file for the application to the root folder of a USB 2 0 drive The package file name is the following VEC100 StgHTG StgCLG_xxxx pkg Note Ensure that the USB drive is formatted as FAT or FAT32 4 Insert the USB drive into the USB port on the VEC 5 If the download does not start immediately then in the c...

Page 4: ...COBP wiring diagram Figure 6 Changeover bypass wiring diagram VEC100 VEC100 Generic RTU Controller Staged Heating and Staged Cooling Quick Start Guide 4 ...

Page 5: ...ne humidity sensor monitor only optional ZN H Table 4 Changeover bypass wiring diagram Number Description Object name if given 17 Return air CO2 Range 0 ppm to 2 000 ppm 0 VDC to 10 VDC RA CO2 18 Return air temperature sensor RA T 19 Outside air temperature sensor Note This is a required sensor if the VEC100 controls the economizer Position the sensor in a shaded area on the north side of the buil...

Page 6: ...VAV wiring diagram Figure 7 VAV wiring diagram VEC100 VEC100 Generic RTU Controller Staged Heating and Staged Cooling Quick Start Guide 6 ...

Page 7: ...ir Proving Switch Setup Selects the type of setup for airflow proof Adjustable None 0 Fan Status Device 1 Duct Static Pressure Sensor 2 None Equalize Cooling Stages Runtime Enables the compressors to run in lead lag mode based on runtime Adjustable No 0 No 1 Yes OAT Cooling Lockout Temperature Sets the temperature at which outside cooling lockout occurs Adjustable 50 F 10 C 0 F to 100 F 18 C to 38...

Page 8: ...I JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Contact information Contact your local branch office www johnsoncontrols com locations Contact Johnson Controls www johnsoncontrols com contact us 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of docum...

Reviews: