Engineering manual - UniSAB III 1.10.8
160/346
001930 en 2021.06
I/O
type
No.
Screw
compressors
Reciprocating
compressors
SABCube
Chiller
Digital
output
1
Compressor motor
start signal
Compressor motor
start signal
(Compressor motor
start signal)
-
2
Oil pump start
signal
Oil rectifier
-
-
3
Oil pump 2/cooling
fan start signal
Additional steps
valve B
Water pump start
signal
-
4
-
-
POV valve
-
5
Shutdown
Shutdown
Shutdown
-
6
Alarm
Alarm
Alarm
-
7
Aux. output
Aux. output
Aux. output
-
8
Start request (PMS)
Start request (PMS)
Start request (PMS)
-
9
Capacity down
Capacity stage no. 1/
Total unload – addi-
tional steps valve A
-
-
10 Capacity up
Capacity stage no. 2/
Valve for thermo
pump
-
-
11 Volume
Capacity stage no. 3/
Valve for thermo
pump/ Thermo pump
shaft end
SSSTV valve
activate
-
12 Volume up
Capacity stage no. 4/
Thermo pump shaft
end
Vi slide activate
-
13 Economiser - suction
line
Capacity stage no. 5
-
-
14 Economiser – liquid
line
Capacity stage no. 6
-
-
15 Oil distribution pipe
Capacity stage no. 7/
Intermediate liquid
injection
Bypass valve
-
16 Oil cooling (Dual HLI
2 cooling when Vi >
85%)
Oil cooling (oil temp.)
Thermo pump
internal
-
Bypass function
(start unload)/Stop
valve for level control
17 Oil cooling (HLI cool-
ing stop valve)
Water cooling (dis-
charge temp.)
Thermo pump
internal
-
-
18 Oil rectifier (Marine)
Oil return
-
Oil return from
evaporator
19
-
-
-
Oil return from
separator
20 Heating elements
-
-
-
Table 34: Numbering of digital outputs