Suction gas superheater - HXSG-type

Material specification

Description

Material specification

Shell

P235GH EN 10216-2

or

P235GH EN 10217-2

or

P265GH EN 10216-2

or

St 35.8 DIN 17175

or

P265GH EN 10217-2

or

St 45.8 DIN 17175

or

SA-333 Gr. 6

Tube plate

P265GH EN 10028-2

Reducer

P235GH EN 10216-2

or

P235GH EN 10217-2

or

P265GH EN 10216-2

or

St 35.8 DIN 17175 or P265GH EN 10217-2

or

St 45.8 DIN 17175

or

SA-333 Gr. 6

Nozzle

P235GH EN 10216-2

Tubes

E235+N EN 10305-4

or

St 37.4 DIN 1630

Or similar.

Connection

nominal

diameter

Connection

external

diameter

OD

Standard

connection

thickness

DIN 2448

Connection possibilities

DN

inch

ANSI SCH40

x cut off

ANSI SCH80

y cut off

15

1/2

21.3

2.3

7

11

20

3/4

26.9

2.3

7

11

25

1

33.7

2.6

8

13

32

1 1/4

42.4

2.6

9

14

40

1 1/2

48.3

2.6

9

15

50

2

60.3

2.9

9

16

65

2 1/2

76.1

2.9

20

22

80

3

88.9

3.2

14

23

100

4

114.3

3.6

15

25

Shipping

The vessel must be blanked off and primed on delivery. The primer is not intended for outdoor
storage. If the vessel is not put into immediate service, take precautions against corrosion or
contamination.

Only lift the vessel when it is empty, and make sure it is not subjected to strokes or bumps dur-
ing transport. When lifting the vessel before it is built into the unit, always use straps around
the shell.

The weight is stated in the technical data.

A shipping description can be made when the vessel is built together with the unit.

Temporary seal cap.

OD

Cut off = Standard marking line

X Cut off = SCH 40

Y Cut off = SCH 80

Std. thickness

DIN 2448