Operating manual - HeatPAC with reciprocating compressor
009332 en 2021.07
45/62
Drop in oil temperature
Cause
Solution
Wet suction gas due to too high R717
charge
Reduce charge.
Wet suction gas due to fluctuating load
Check secondary system.
Wet suction gas due to quick changes in
compressor capacity
Adjust settings for load/unload compressor capacity in
UniSAB III.
Too much compressor cooling
Reduce water flow or temperature to compressor cooling.
See compressor manual for more information.
5.6.3
Testing of HeatPAC units
HeatPAC units supplied by Johnson Controls Denmark have, as far as possible, been function and per-
formance tested.
A performance test consists of simultaneous measurements of cooling or heating capacity, power con-
sumption and condenser capacity.
It is not a simple task to measure performance. High quality measuring and logger equipment is required
to make reliable and accurate measurements. Contact a Johnson Controls Denmark representative if a
performance test is needed.