System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin
53
2. In the
Analog Output Setup Start (OUTA
x
)
screen, press to go to the
Select Sensor (SENs
x
)
screen. (The Select Sensor screen does not appear here
if the sensor is already selected for this output. In that case, go to the next step.)
Press or to select the hard-wired or functional sensor (Sn-1, Sn-2, Sn-3,
Sn-d, HI-2, or HI-3) that the output references. Press to save the sensor
selection and go to the
Select Setpoint Value screen.
3. In the
Select Setpoint Value (SP
x
)
screen, press or to select the Setpoint
value. (The controlled system drives towards Setpoint [SP] and away from End
Point [EP], which together define the proportional band for the analog output.)
Press to save the Setpoint value and go to the next screen.
Note:
If you selected the
Sn-d
Select Differential Setpoint
Value (dSP
x
)
screen is displayed. Press or to select the temperature,
pressure, or humidity differential value towards which the controlled
system is driving. Press to save the dSP value and go to the
Select
Differential End Point Value (dEP
x
)
screen. (See
page 25 for more information.)
4. In the
Select
End Point Value (EP
x
)
screen, press or to select the End
Point value. (The controlled system operates between Setpoint and End Point,
which together define the proportional band for the analog output.) Press to
save the End Point value and go to the next screen.
Note:
If you selected the
Sn-d
Select Differential End
Point Value (dEP
x
)
screen is displayed, press or to select the
differential End Point value. (The controlled system operates between
differential Setpoint and differential End Point, which together define the
proportional band for the analog output.) Press to save the dEP value and
go to the next screen. (See
information.)
5. In the
Select
Output Signal Strength at Setpoint (OSP
x
)
screen, press or
to select the value in percent of the output signal strength (0 to 100%),
corresponding to the lowest output capacity, when the sensor is at Setpoint
(SP
x
). Press to save the displayed OSP value and go to the next screen.
6. In the
Select
Output Signal Strength at End Point (OEP
x
)
screen, press or
to select the value in percent of the output signal strength (0 to 100%),
corresponding to the highest output capacity, when the sensor is at the End
Point (EP
x
). Press to save the displayed OEP value and go to the next screen.
7. In the
Select
Integration Constant (I-C
x
)
screen, press or to select the
integration constant value for the analog output. (See
Integration Constant for an Analog Output
on page 56 for more information.)
Press to save the displayed I-C value and go to the next screen.