Johnson Controls Ducted Systems
3
LIMITATIONS
These units must be installed in accordance with the following:
In U.S.A:
• National Electrical Code, ANSI/NFPA No. 70 - Latest Edition
• National Fuel Gas Code, ANSI Z223.1 - Latest Edition
• Gas-Fired Central Furnace Standard, ANSI Z21.47a. - Latest Edi-
tion
• Local building codes
• Local gas utility requirements
In Canada:
• Canadian Electrical Code, CSA C22.1
• Installation Codes, CSA - B149.1
• Local plumbing and waste water codes
• Other applicable local codes
See the unit application data found in this document.
After installation, gas fired units must be adjusted to obtain a temperature
rise within the range specified on the unit rating plate.
If it is necessary to add components to a unit to meet local codes, instal-
lation is done at the dealer’s and/or customer’s expense.
The size of the unit for proposed installation must be based on heat
loss/heat gain calculation made according to the methods of Air Condi-
tioning Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings or
structures under construction.
Table 1:
Unit Limitations
Model
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Minimum
Maximum
Maximum (°F)
PCG4A24
208/230-1-60
187
252
125
PCG4A30
208/230-1-60
187
252
125
PCG4A36
208/230-1-60
187
252
125
PCG4A42
208/230-1-60
187
252
125
PCG4B48
208/230-1-60
187
252
125
PCG4B60
208/230-1-60
187
252
125
Table 2:
Application Limitations
Packaged Equipment Series
Air Temperature at Outdoor Coil (°F)
Air Temperature at Indoor Coil (°F)
Minimum
Maximum
Minimum
Maximum
DB Cool
DB Cool
WB Cool
WB Cool
14 SEER AC
55
125
57
72
FIGURE 1:
Component Location
FAN MOTOR
OUTDOOR FAN
COIL GUARD PANEL
OUTDOOR COIL
(Behind Panel)
CONTROL BOARD
TRANSFORMER
HIGH VOLTAGE
CONTACTOR
PRESSURE SWITCH
DRAFT INDUCER BLOWER
GAS VALVE
BURNER
ASSEMBLY
GAS HEAT
EXCHANGER
BLOWER MOTOR
TXV
INDOOR COIL
INDOOR BLOWER
COMPRESSOR
REMOVABLE
BASE RAILS
A0297-001