background image

      

INSTALLATION GUIDE

I

nstalling and Operating the ESUSA Repeater

INTRODUCTION

The ESUSA Repeater is an unintelligent
router used solely for passing information
and adding length to an existing L

ON

W

ORKS

network.  It will not filter network packets.

ECHELON

FTT
-10A

50051

G9441B

ECHELON

FTT
-10A

50051

G9441B

5.00ECSD

JP2

BUS

FREE

JP1

BUS

FREE

Figure 1 - Repeater board shown in enclosure with

cover removed.

INSTALLATION

The repeater connects to the L

ON

W

ORKS

network via a suitable network cable. The
repeater is powered by a separate power
supply.  See Wiring Recommendations.

Wiring

WARNING - TO PREVENT

ELECTRICAL SHOCK OR DAMAGE

TO THE EQUIPMENT, YOU MUST

DISCONNECT THE POWER

SUPPLY TO THE REPEATER BEFORE YOU

MAKE THE WIRING CONNECTIONS.

All wiring is low voltage and should be in
accordance with local regulations and the
National Electrical Code.

Use shielded cable only when it is required.
Most applications do not require shielding
and will benefit from unshielded cable.

NXE-REP-FTT Repeater

 

 

 Electronic Systems USA             9410 Bunsen Parkway               Louisville, KY 40220            (502) 495-6700

TEC DOC # LIT-TD-2034    11/00

Figure 2 - Wiring connections for the Repeater.

When using the optional shielded cable,
ground only one end of the shield.   Low
voltage control wiring should not be run in
the same conduit as line voltage wiring or
other conductors that supply highly-
inductive loads (such as contactors, coils,
motors, generators, etc.).

CAUTION - MAKE ALL CONNEC-

TIONS AND CHECK ALL CON-

NECTIONS BEFORE APPLYING

POWER.  IMPROPER WIRING

MAY CAUSE PERMANENT

DAMAGE TO THIS EQUIPMENT.

WIRING RECOMMENDA-

TIONS

Unshielded (Recommended

)

22AWG, Stranded:  Belden #8443 (3-wire),
8444 (4-wire), 8445 (5-wire)
18AWG, Stranded:  Belden #8489(4-wire),
8465(5-wire)
Plenum-rated, 22AWG, Stranded:  Belden
#82444(4-wire), 82743(6-wire)
Plenum-rated, 18AWG, Stranded:  Belden
# 82489(4-wire)

Shielded (Optional)

Stranded:  Belden #8761
Plenum-rated, Stranded:  Belden
#88761

To Wire the Repeater:

The terminal block slides into the slot on the
right side of the board.  Refer to Figure 2.

1

. Orient the terminal block as if you will

mount it on the board.

2

.  Wire the two Net A wires in the top

two positions of the terminal block.

3

.  Connect the ground wire via the third

screw on the terminal block.

4

.  Connect the 24VAC hot wire to the

forth terminal screw.

5

.  Wire the two Net B wires into the

bottom two positions of the terminal
block.

NOTE:  Network wiring is polarity inde-

pendent, but the drawing indicates
Net - and Net + to accommodate the
conventions of circuitry design.

Copyright ©2000. Electronic Systems USA        All Rights Reserved.

NET  A  -

NET  A +

24VAC  NEU
24VAC  HOT

NET  B  -
NET  B +

Net A

Net B

Net B

Ground

24 VAC Hot

Net A

Note

:  Network wiring is polarity independent.

Reviews: