NS Series Network Discharge Air Sensors Installation Instructions
3
Note:
For more details on wiring the MS/TP
Communications Bus, refer to the
MS/TP
Communications Bus Technical Bulletin
(LIT-12011034)
or the
FX-PC Series Controllers
MS/TP Communications Bus Technical Bulletin
(LIT-12011670)
.
6.
Use the Metasys® Controller Configuration
Tool (MS-CCT) or Facility Explorer Programmable
Controller Tool (FX-PCT) Software to commission
the discharge sensor. Refer to the Controller
Tool
Help (LIT-12011147)
for more details.
Repair Information
If the NS Series Network Discharge Air Sensor fails to
operate within its specifications, replace the unit. For a
replacement discharge air sensor, contact the nearest
Johnson Controls representative.
Risk of Electric Shock.
Disconnect the power supply before making electrical
connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
IMPORTANT:
Failure to adhere to these wiring
details causes the discharge air sensor to function
incorrectly.
Figure 2: Wiring to the SA Bus
Screw Terminal Block