Commissioning
Use the following procedure to commission the
VMA1615/1630 controller:
1. Download the control application to the VMA controller
using the Controller Configuration Tool (CCT). Refer
to the
Controller Tool Help (LIT-12011147)
.
2. Commission the VAV Box. Refer to the
Controller
Tool Help (LIT-12011147)
.
3. Perform airflow balancing on the VAV box. Refer to
the
VAV Balancing Tool Technical Bulletin
(LIT-12011087)
.
4. Perform commissioning checkout procedures. Refer
to the Controller Tool
Help (LIT-12011147)
.
Repair Information
The MS-VMA1615-xU and MS-VMA1630-xU models are
UL 864 10th Edition UUKL/ORD-C100-13 UUKLC listed
for smoke control. If the VMA1615/1630 controller fails
to operate within its specifications, contact the Johnson
Controls Repair Center in Louisville, Kentucky, at
1-502-671-7312.
Troubleshooting
provides LED status indicator information for
troubleshooting the VMA1615/1630 controller.
provides some additional troubleshooting information for
possible problems.
Note:
If you experience short circuits in the 24 VAC
power supply causing protective devices such as
breakers or fuses to trip, make sure that the power
connections on the VMA are not reversed. The
most common cause of this problem is when the
24 VAC power supply on the VMA is reversed but
not reversed on a connected secondary device.
Improper wiring of this power terminal may cause
a short circuit across the 24 VAC power supply
on -1 models.
17
VMA1615 and VMA1630 Variable Air Volume Controllers Installation Instructions