FEU16x0 Field Equipment Controller Installation Instructions
9
24~ Power
Hot
AC Supply Input
Supply 20-30 VAC (Nominal 24 VAC)
0.8 mm to 1.0 mm
(20 to 18 AWG) 2-wire
SHLD
Provides an optional shield connection.
1.
for alternative wire gauges and lengths.
2.
The SA Bus terminals and the RJ-style modular Sensor Port are connected internally.
3.
The SA Bus and FC Bus specifications in this table are for MS/TP bus communications at 38.4k baud. For more
information, refer to the
MS/TP Communications Bus Technical Bulletin (LIT-12011034)
.
Table 2: Wire Gauge and Length Guidelines
Guideline
Cable Size
Maximum
Length
Assumptions
A
1.0 mm (18 AWG)
457.2 m (1,500 ft)
100 mV maximum voltage drop
0.8 mm
(20 AWG)
297.2 m (975 ft)
0.6 mm
(22 AWG)
182.9 m (600 ft)
0.5 mm (24 AWG)
106.7 m (350 ft)
B
1.0 mm (18 AWG)
228.6 m (750 ft)
100 mV maximum voltage drop
0.8 mm
(20 AWG)
137.1 m (450 ft)
0.6 mm
(22 AWG)
91.4 m (300 ft)
0.5 mm (24 AWG)
61 m (200 ft)
C
See
N/A
Table 1: FEC Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 3 of 3)
Terminal
Block
Terminal
Labels
Function and Electrical Ratings/Requirements
Recommended Cable Type
and Length
1