Technical Specifications

M9220-GGx Proportional Electric Spring Return Actuators (Part 1 of 2)

Power Requirements

AC 24 V (AC 19.2 to 30 V) at 50/60 Hz: Class 2 (North America) or SELV 
(Europe), 15.5 VA running, 7.7 VA holding position; 
DC 24 V (DC 21.6 to 26.4 V): Class 2 (North America) or SELV 
(Europe), 6.7 W running, 2.9 W holding position

Transformer Sizing Requirements

20 VA minimum per actuator

Input Signal/Adjustment

Factory set at DC 0 to 10 V, CW Rotation with signal increase;
Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with field furnished 
500 ohm, 0.25 W minimum resistor;
Switch selectable direct or reverse action with signal increase

Control Input Impedance

Voltage Input: 100,000 ohms;
Current Input: 500 ohms with Field Furnished 500 ohm resistor

Feedback Signal

DC 0 (2) to 10 V for desired rotation range up to 90°;
Corresponds to rotation limits, 1 mA maximum

Auxiliary Switch Rating

GGC Models

Two Single-Pole, Double-Throw (SPDT), double-insulated switches with 
gold flash contacts:
AC 24 V, 50 VA Pilot Duty; 
AC 120 V, 5.8 A resistive, 1/4 hp, 275 VA Pilot Duty; 
AC 240 V, 5.0 A resistive, 1/4 hp, 275 VA Pilot Duty

Spring Return

Direction is selectable with mounting position of actuator: 
Side A, actuator face away from damper for CCW spring return; 
Side B, actuator face away from damper for CW spring return

Running and Spring Return Torque

177 lb·in (20 N·m) for a single actuator; 
354 lb·in (40 N·m) for two like models mounted in tandem
531 lb·in (60 N·m) for three like models mounted in tandem

Rotation Range

Adjustable from 30 to 90° CW or CCW with optional 
M9220-603 Adjustable Stop Kit; mechanically limited to 90°

Rotation Time

Power On 
(Running)

150 seconds for 0 to 177 lb·in (0 to 20 N·m) at all operating conditions; 
independent of load
90 seconds for 0 to 177 lb·in (0 to 20 N·m) in calibration mode or override 
mode

Power Off 
(Spring
Returning)

11 to 15 seconds for 0 to 177 lb·in (0 to 20 N·m) at room temperature; 
35 seconds maximum for 0 to 177 lb·in (0 to 20 N·m) at -22°F (-30°C)
130 seconds maximum for 0 to 177 lb·in (0 to 20 N·m) at -40°F (-40°C)

Cycles

60,000 full stroke cycles; 1,500,000 repositions

Audible Noise Rating

Power On 
(Running)

<45 dBA at 39-13/32 in. (1 m)

Power On 
(Holding)

<20 dBA at 39-13/32 in. (1 m)

Power Off 
(Spring
Returning)

<55 dBA at 39-13/32 in. (1 m)

Electrical Connections

Actuator
(All Models)

48 in. (1.2 m) halogen-free cable with 18 AWG (0.75 mm

2

) wire leads

Auxiliary 
Switches 
(GGC Models)

48 in. (1.2 m) halogen-free Cable with 18 AWG (0.75 mm

2

) wire leads

Conduit Connections

Integral connectors for 3/8 in. (10 mm) flexible metal conduit

Summary of Contents for M9220-GGx-3 series

Page 1: ...3 Proportional Electric Spring Return Actuator only to control equipment under normal operating conditions Where failure or malfunction of the electric actuator could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or s...

Page 2: ...ical connections and wiring details are also included on the actuator housing Parts Included proportional electric spring return actuator with coupler anti rotation bracket manual override crank two M3 x 9 5 mm self drilling sheet metal mounting screws two No 10 32 x 9 16 in thread forming conduit screws Special Tools Needed torque wrench with 3 8 in 10 mm socket digital voltmeter or M9000 200 Com...

Page 3: ...mensions Figure 1 M9220 GGx 3 Proportional Electric Spring Return Actuator Dimensions in mm A 4 102 10 5 16 262 2 3 16 56 FIG M9210_9220_dimen 1 3 4 44 1 8 3 3 3 16 81 3 4 19 2 3 16 56 1 25 2 51 1 19 32 40 1 1 16 27 1 4 6 5 Mounting Hole 6 Locations 1 19 32 40 1 19 32 40 6 15 16 176 10 254 ...

Page 4: ...re for protecting a single M9210 20 actuator from rain sleet or snow quantity 1 M9000 400 Jackshaft Linkage Kit Open ended design enables clamping onto a jackshaft without requiring access to the ends of the jackshaft quantity 1 M9000 519 Valve linkage for mounting M9220 actuator to 2 1 2 to 6 in flanged ball valves M9000 604 Replacement Anti rotation Bracket Kit with screws for M9210 xxx 3 Series...

Page 5: ...ns CW Removable Coupler The coupler may be installed on either side of the output hub If the damper shaft is less than 3 19 32 in 91 mm long insert the coupler in the face of the actuator closest to the damper If the damper shaft is shorter than 1 5 32 in 29 mm long a shaft extension is required to mount the actuator Figure 2 Side A of Actuator A 90 5 10 20 30 40 50 60 70 80 Manual Override Pointe...

Page 6: ...osite direction to lock the actuator hub in place Note To unlock the actuator hub rotate the manual override crank in the direction indicated by the arrow on the label The actuator hub automatically unlocks when power is applied to the actuator and returns the actuator to normal drive and spring return operation Mounting the Actuator To mount the actuator proceed as follows 1 See the dimensions in...

Page 7: ...nough for the actuator to travel a full stroke and verify that the actuator rotates freely throughout the range Note If electric power is not available complete this verification by reinserting the manual override crank and turning it in the direction indicated to rotate the coupler to the fully open position Rotation Range Using Optional M9220 603 Adjustable Stop Kit The actuator is factory set f...

Page 8: ...onal end stops are available to limit the output hub travel An anti rotation bracket prevents rotational movement of the actuator body See Figure 9 Figure 10 and Figure 11 for proper wiring of the M9220 GGx 3 Proportional Electric Spring Return Actuator Figure 8 One Stroke Limiting Stop Mounted in the Minimum Stroke Position for a Rotation Range of 65 A 90 5 10 20 30 40 50 60 70 80 Sweep Angle Ind...

Page 9: ... Override to MIN position AC 24 V DC 0 2 10 V DC 0 2 10 V A A Open MIN Position A Closed Normal Operation 1 2 3 4 Y COM U BLK RED GRY ORN Override to MAX position AC 24 V DC 0 2 10 V DC 0 2 10 V C B Closed MAX Position C Closed Normal Operation B 1 2 3 4 COM U BLK RED GRY ORN Override to MIN MID MAX positions 0 4 20 mA Control with External Resistor AC 24 V A 0 4 20 mA 500 0 25 W B C 1 2 3 4 COM U...

Page 10: ...rotation range The actuator stores the reduced rotation range in nonvolatile memory retains data when power is lost or removed To calibrate the control input range proceed as follows 1 With power off move the mode selection switch to the CAL position Figure 13 Then energize the actuator The actuator automatically rotates until the end stops are found and proportionally reconfigures the control inp...

Page 11: ...ch actuator Total Power Number of Actuators x Running Power x 1 5 Only one of the actuators can be configured as the master Set the selector switch to the master position Figure 15 The other GGx actuator s must be configured as slave s by setting the tandem selector switch to the slave position The master can accept DC 0 10 V or DC 2 10 V or 4 20 mA command signals based on the master s switch set...

Page 12: ... No 1 is 11 closing and the nominal factory setting for Auxiliary Switch No 2 is 81 opening relative to a 0 to 90 rotation range See the Technical Specifications table for the auxiliary switch ratings The switch point of Auxiliary Switch No 1 is fixed The switch point of Auxiliary Switch No 2 is independently and continuously adjustable from 25 to 95 See Figure 17 and use the method in the followi...

Page 13: ...e fully open position and holds while power is applied 4 Observe the switch point If required repeat Steps 2 and 3 Repairs and Replacement A number of replacement parts are available see Table 1 for more details If the M9220 GGx 3 Proportional Electric Spring Return Actuator fails to operate within its specifications replace the unit For a replacement electric actuator contact the nearest Johnson ...

Page 14: ...Direction is selectable with mounting position of actuator Side A actuator face away from damper for CCW spring return Side B actuator face away from damper for CW spring return Running and Spring Return Torque 177 lb in 20 N m for a single actuator 354 lb in 40 N m for two like models mounted in tandem 531 lb in 60 N m for three like models mounted in tandem Rotation Range Adjustable from 30 to 9...

Page 15: ...icular Requirements for Electric Actuators Models All Canada UL Listed CCN XAPX7 File E27734 to CAN CSA E60730 1 Automatic Controls for Household and Similar Use and CAN CSA E60730 2 14 Part 2 Particular Requirements for Electric Actuators Models All Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the ...

Reviews: