10
M9216 Series Electric Spring Return Actuators Installation Instructions
Technical Data
Product
M9216 Series Electric Spring Return Actuators
Power Requirements
AGx, HGx, JGx: 20 to 30 VAC at 50/60 Hz or 24 VDC ±10%, 12 VA supply, Class 2
BGx:
20 to 30 VAC at 50/60 Hz or 24 VDC ±10%, 10 VA supply, Class 2
GGx:
20 to 30 VAC at 50/60 Hz or 24 VDC ±10%, 14 VA supply from 32 to 122°F
(0 to 50°C) or 18 VA supply from -22 to 32°F (-30 to 0°C), Class 2
Input Signal
AGx:
24 VAC at 50/60 Hz or 24 VDC, 4.8 mA (on/off mode, 500 mA maximum)
BGx:
24 VAC at 50/60 Hz or 24 VDC, 420 mA maximum
GGx, HGx:
0 to 10 VDC or 0 to 20 mA
JGx:
Potentiometer value is 100 ohms minimum to 10,000 ohms maximum
Input Signal Adjustments
AGx Factory Setting:
Terminals 1 and 3, CW rotation; Terminals 1 and 4, CCW rotation
BGx Factory Setting:
Terminals 1 and 2, CW rotation
GGx (Voltage or Current Input):
Switch Selectable: 0 (2) to 10 VDC or 0 (4) to 20 mA
Factory Setting:
0 to 10 VDC, CW rotation with signal increase
HGx (Voltage Input or Current Input):
Jumper Selectable, Fixed:
0 (2) to 10 VDC or 0 (4) to 20 mA
Adjustable: Zero, 0 to 6 V (0 to 12 mA); Span, 2 to 10 V (4 to 20 mA)
Factory Setting:
0 to 10 VDC, 0 to 20 mA, CW rotation with signal increase
GGx, HGx, JGx:
Direction of action is user selectable Direct (CW) or Reverse (CCW)
with signal increase.
Input Impedance
GGx, HGx:
Voltage Input, 200,000 ohms; Current Input, 500 ohms
JGx:
1.8 Megohms
Feedback Signal
AGD:
135 ohm feedback potentiometer
AGE:
1,000 ohm feedback potentiometer
GGx, HGx:
0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA)
Corresponds to input signal span selection and rotation limits.
JGx:
0 to 10 VDC for 90° (10 VDC at 1 mA)
Auxiliary Switch Rating
xGC:
Two SPDT (Single-Pole, Double-Throw) rated at 24 VAC, 1.5 A inductive,
3.0 A resistive, 35 VA maximum per switch, Class 2
Spring Return
Factory Setting: CCW; Direction is selectable with the coupler.
Mechanical Output
(Running Torque)
All Models:
140 lb∙in (16 N∙m) for one unit
BGx, GGx, HGx:
280 lb∙in (32 N∙m) for two units in tandem
Rotation Range
Adjustable from 30 to 90°, CW or CCW, mechanically limited to 93°
Rotation Time
70 to 130 seconds for 0 to 140 lb
∙in (0 to 16 N∙m); 90 seconds nominal at 50% rated load
(Powered rotation is faster in the spring return direction than in the spring winding direction;
power failed spring return is less than 15 seconds.)
Cycles
65,000 full stroke cycles
Electrical Connection
GGx:
1/4 in. spade terminals with pluggable terminal blocks
All Other Models: Screw terminals for 22-14 AWG; maximum of two 18, 20, or 22 AWG each
M9000-100:
One included with all models; two included with AGD, AGE, and xGC
Mechanical Connection
3/8 to 3/4 in. (10 to 20 mm) diameter round shaft; 3/8 to 5/8 in. (10 to 16 mm) square shaft
Enclosure
NEMA 2, IP42
Ambient Conditions
Operating, GGx:
-22 to 122°F (-30 to 50°C); 0 to 95% RH, non-condensing
All Other Models: -4 to 122°F (-20 to 50°C); 0 to 95% RH, non-condensing
Storage, All Models:
-40 to 186°F (-40 to 86°C); 0 to 95% RH, non-condensing
Dimensions (H x W x D)
9.82 x 4.57 x 3.62 in. (249.4 x 116.0 x 91.9 mm)
Shipping Weight
6.4 lb (2.9 kg)
Agency Compliance
UL 873 Listed, File E27734, CCN XAPX
CSA C22.2 No. 139 Certified, File LR85083, Class 3221 02
CE Mark, EMC Directive 89/336/EEC
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423
Printed in U.S.A.
Milwaukee, WI 53201