Johnson Controls M9203-AG-2 Series Installation Manual Download Page 8

M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Guide

8

Control Response

The installation side of the actuator and the position of 
the mode selection switch combine to determine 
control response from the actuator. See Figure 13.

Auxiliary Switch (M9203-xxB-2(Z) Models)

The M9203-xxB-2(Z) models include one integral 
auxiliary switch with a switch adjuster accessible on 
either face of the actuator (see Figure 2 and Figure 3)
The factory setting for the Auxiliary Switch is 
11° closing (relative to the 0 to 90° rotation range as 
printed on the product label). See the 

Technical 

Specifications

 table for the auxiliary switch ratings. 

The switch point is continuously adjustable throughout 
the actuator’s rotation range. For the most accurate 
switch positioning, see Figure 14 and use the method 
in the following example.

To change the switch point, proceed as follows:

1. Position the actuator in the full spring return 

position.

Note:

The switch is factory set to trip when the 

actuator reaches the 11° position.

2. Rotate the switch adjuster until it points to the 

desired switch point.

3. Connect the Auxiliary Switch to a power source or 

an ohmmeter and apply power to the actuator. The 
actuator moves to the fully open position and holds 
while power is applied.

4. Observe the switch point. If required, repeat Step 1 

through Step 3.

Repair Information

A number of replacement parts are available; see 
Table 1 for more details. If an M9203-AGx-2(Z) Series
On/Off and Floating Point Control Electric Spring 
Return Actuator fails to operate within its specifications, 
replace the unit. For a replacement electric actuator, 
contact the nearest Johnson Controls representative.

!

WARNING: Risk of Electric Shock and 
Property Damage.

Insulate and secure each unused wire 
lead before applying power to the 
actuator. Failure to insulate and secure 
each unused wire lead may result in 
property damage, electric shock, and 
severe personal injury or death.

AVERTISSEMENT : Risque de 
décharge électrique et dégâts 
matériels.

Isoler et protéger chaque fil non utilisé 
avant de mettre l'actuator sous tension. 
Le non-respect de cette obligation 
d'isolation et de protection de chaque fil 
non utilisé risque d'entraîner des dégâts 
matériels, des décharges électriques et 
des blessures graves, voire mortelles.

Figure 13:  Control Response

FI

G

:M

92

xx

A

Gx

_C

tr

lR

spns

Control Inputs

GRY

ORN

Mode Selection Switch

3

4

Installation Side

90

70

10

50 30

30

90

50

70

30

90

50

70

10

Figure 14:  Switch Trip Point Settings

30

90

50

70

30

90

50

70

10

Switch Adjuster

FI

G

:s

w

tc

h_

st

tn

g

Summary of Contents for M9203-AG-2 Series

Page 1: ...the actuator No additional linkages or couplers are required Electrical connections are color coded and identified with numbers permanently marked on the actuator cable A tag on the actuator cable identifies the electrical connections and wiring details are included on the actuator housing IMPORTANT Use this M9203 AGx 2 Z Series On Off and Floating Point Electric Spring Return Actuator only to con...

Page 2: ... this M9203 AGx 2 Z Series On Off and Floating Point Electric Spring Return Actuator in or near environments where corrosive substances or vapors could be present Exposure of the electric actuator to corrosive environments may damage the internal components of the device and will void the warranty Figure 1 M9203 AGx 2 Series On Off and Floating Point Electric Spring Return Actuator Dimensions in m...

Page 3: ...9000 560 Ball Valve Linkage Kit for applying M9104 M9203 and M9208 Series Electric Actuators to VG1000 Series Valves quantity 1 M9000 561 Thermal Barrier Kit for M9000 560 Ball Valve Linkage Extends M VA 9104 M VA 9203 M VA 9208 and M VA 9308 9310 Series Electric Actuators applications to include low pressure steam quantity 1 M9000 604 Replacement Anti Rotation Bracket Kit for M9203 M9208 M9220 an...

Page 4: ... to the damper If the damper shaft extends less than 0 79 in 20 mm a shaft extension is required to mount the actuator To change the coupler s position see Figure 4 and proceed as follows 1 Mount the coupler on either Side A or Side B of the actuator as determined by the shaft length 2 Snap the locking clip securely into the coupler retention groove to retain the coupler Mounting the Actuator To m...

Page 5: ... coupler side of the actuator to reduce the rotation range Attaching the stroke limiting stop in the furthest mounting position reduces the rotation range of the actuator by 5 Each progressive mounting position reduces the rotation range an additional 5 1 Check that the damper blade is visible or its position is permanently marked on the end of the damper shaft as illustrated in Figure 7 2 Positio...

Page 6: ...ltage can cause electric shock and may result in severe personal injury or death AVERTISSEMENT Risque de décharge électrique Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique Plusieurs isolations et débranchements sont peut être nécessaires pour couper entièrement l alimentation de l équipement Tout contact avec des composants conducteurs de tensions dangereuses r...

Page 7: ... can be switched by the user to Reverse Acting RA mode CAUTION Risk of Property Damage Insulate and secure each unused wire lead before applying power to the actuator Failure to insulate and secure each unused wire lead may result in property damage MISE EN GARDE Risque de dégâts matériels Isoler et protéger chaque fil non utilisé avant de mettre l actuator sous tension Le non respect de cette obl...

Page 8: ... and apply power to the actuator The actuator moves to the fully open position and holds while power is applied 4 Observe the switch point If required repeat Step 1 through Step 3 Repair Information A number of replacement parts are available see Table 1 for more details If an M9203 AGx 2 Z Series On Off and Floating Point Control Electric Spring Return Actuator fails to operate within its specifi...

Page 9: ...ole Double Throw SPDT Double Insulated Switch with Silver Contacts AC 24 V 50 VA Pilot Duty AC 120 V 5 8 A Resistive 1 4 hp 275 VA Pilot Duty AC 240 V 5 0 A Resistive 1 4 hp 275 VA Pilot Duty Spring Return Direction Is Selectable with Mounting Position of Actuator Actuator Face Labeled A Is Away from Damper or Valve CCW Spring Return Actuator Face Labeled B Is Away from Damper or Valve CW Spring R...

Page 10: ...tandard Operating 22 to 140 F 30 to 60 C 90 RH Maximum Noncondensing Storage 40 to 185 F 40 to 85 C 95 RH Maximum Noncondensing Dimensions 6 38 x 3 23 x 2 26 in 162 x 82 x 57 5 mm Compliance United States UL Listed CCN XAPX File E27734 to UL 60730 1A 2003 08 Ed 3 1 Automatic Electrical Controls for Household and Similar Use and UL 60730 2 14 2002 02 Ed 1 Part 2 Particular Requirements for Electric...

Page 11: ...t warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Patents Patents http jcipat com Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MIC...

Reviews: