Table 7: Communication bus and supply power terminal blocks, functions, ratings, requirements, and
cables
Terminal block/Port label
Terminal labels
Function, electrical ratings/
Requirements
Recommended cable type
FC BUS (Port)
FC BUS
RJ-12 6-Position Modular Port provides
FC Bus Communications.
FC Bus provides 15 VDC Power for:
•
Wireless Bluetooth
Commissioning Converter
(BTCVT)
2
•
Wireless ZigBee Field Bus Router
24 AWG 3-pair CAT 3 Cable <30.5m
(100 ft)
+
-
SA Bus Communications
COM
SA Bus Signal Reference and 15 VDC
Common
SA BUS
SA PWR
15 VDC Supply Power for Devices on the
SA Bus
0.6 mm (22 AWG) stranded, 4-wire
(2 twisted-pairs), shielded cable
recommended
Note:
The + and - wires are one
twisted pair, and the COM and
SA PWR wires are the second
twisted pair.
SA BUS (Port)
SA BUS
RJ-12 6-Position Modular Port provides
SA Bus Communications.
SA Bus provides 15 VDC Power for the
following:
•
NS Series Sensors
•
MAP Gateway 4.2 or above
•
Wireless ZigBee WRZ-78xx Series
One-to-One Wireless Receiver
•
Wireless Bluetooth
Commissioning Converter
(BTCVT)
•
DIS1710 Local Controller Display
•
VAV Balancing Tool
24 AWG 3-pair CAT 3 Cable <30.5m
(100 ft)
HOT
24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24VAC)
24~
COM
24 VAC Power Supply Common
The CVM models only isolate this
terminal from the FC bus common.
0.8 mm to 1.0 mm
(20 to 18 AWG) 2-wire
1
The FC bus and SA bus wiring recommendations in this table are for MS/TP Bus communications at 38.4k baud.
2
The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.
M4-CVM03050 VAV Controllers Installation Guide
12