SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
6
SETPOINTS
All “Setpoints” values are numeric. To view the val-
ues press the SETPOINTS key. After pressing the
SETPOINTS key use the ◄ key or the ► key to se
-
lect the menu subsection: Unit, Cooling, Compressor
Systems, Supply System, Heating, Economizer, Ven-
tilation, or Condenser, that contains the parameter you
would like to view. The parameters contained under
each of these menu subsections and their password
level is contained in
▲
and
▼
arrow
key to navigate to the parameter within the subsection
you want to view.
If you need to change any of the “Setpoints,” press
the CHECK key. The Enter Password screen appears.
All “Setpoints” parameters require the use of a pass-
word before they can be changed.
page 168 for information on how to enter a password
into the User Interface.
If a Level 1 password is en-
tered, only Level 1 setpoint parameters are available
for change. Entering a Level 2 password makes all
setpoint parameters available.
Once a password is entered it remains active for 15
minutes.
TABLE 36 -
SETPOINTS
USER
INTERFACE
KEY
SUBSECTION
DISPLAYED TEXT
RANGE
DEFAULT
VALUE
UNIT
SETTING
Setpoint
Cooling
OCC Zone Cooling
Setpoint
2.0°F above OCC Zone Heating
Setpoint to 85.0°F
72.0°F
Setpoint
Cooling
UNOCC Zone Cooling
Setpoint
2.0°F above UNOCC Zone Heat-
ing Setpoint to 95.0°F
85.0°F
Setpoint
Cooling
RAT Cooling Setpoint
2.0° F above RAT Heating
Setpoint to RAT for High SAT
70.0°F
Setpoint
Cooling
Maximum Bypass
20.0% to 40.0%
40.00%
Setpoint
Cooling
Ist Stage Cooling Setpoint
(SAT SP for CV)
55.0°F to 65.0°F
60.0°F
Setpoint
Cooling
2nd Stage Cooling
Setpoint (SAT SP for CV)
50.0°F to 60.0°F
55.0°F
Setpoint
Cooling
SAT Low Setpoint
50.0°F to SAT High Limit
55.0°F
Setpoint
Cooling
SAT High Setpoint
55.0°F to 65.0°F
65.0°F
Setpoint
Cooling
MX Supply Air Temp
Setpoint
50.0°F to 65.0°F
60.0°F
Setpoint
Cooling
OAT Setpoint for Low SAT
OAT for High SAT to 90.0°F
80.0°F
Setpoint
Cooling
OAT Setpoint for High Sat
60.0°F to OAT for Low SAT
70.0°F
Setpoint
Cooling
RAT Setpoint for Low RAT
RAT Setpoint for High RAT
+ 5.0
°F to 90.0°F
80.0°F
Setpoint
Cooling
RAT Setpoint for High
SAT
RAT Cooling Setpoint to RAT
Setpoint for Low SAT - 5.0°F
70.0°F
Setpoint
Cooling
Fan Speed Setpoint for
Low SAT
Fan Speed Setp for High SAT to
100.0%
90.00%
Setpoint
Cooling
Fan Speed Setpoint for
High SAT
50.0% to Fan Speed Setpoint
for Low SAT
70.00%
Setpoint
Cooling
Evap Leaving Air Temp
High
Evap Leaving Air Temp Low to
60.0°F
60.0°F
Setpoint
Cooling
Evap Leaving Air Temp
Low
50.0°F to Evap Leaving Air
Temp High
50.0°F
Setpoint
Cooling
Reset Enthalpy SP
25 to 35 BTU/LB
30 BTU/LB
Setpoint
Cooling
Return Air Diff SP
4.0°F to 10.0°F
6.0°F