LN-Display Installation Instructions

6

The LN-Display controller also has a built-in network 
jack (1/8 in. [3.5 mm] mono male audio jack) that can 
be used to connect to the L

ON

W

ORKS

 network. This 

network jack is located on the bottom of the device 
(Figure 12).

Selecting Network Terminators

For information on selecting Network Terminators, 
refer to the

 L

ON

W

ORKS

 LN-Series Network 

Communication and Interface Guide Technical Bulletin 
(LIT-12011253)

.

Setup and Adjustments

Commissioning

To commission a device and add it to a L

ON

W

ORKS

 

network, use the device plug-in as well as the .xif and 
.apb files. 

Note:

The device commissioning instructions only 

apply when you are using a L

ON

W

ORKS

 Network 

Services (LNS®) network management tool, such as 
LN-Builder.

To obtain the necessary files:

1.

Run the installation setup to install the device 
plug-in and the latest version of the .xif and .apb 
files onto your computer. The .xif and .apb files 
install in the C:\LonWorks\Import\JCI folder.

2.

Register the plug-in on the network database. By 
doing this, you create the device template that is 
used to commission the device.

3.

Commission the device using the proper device 
template and .apb file with your network 
management tool.

Note:

If you download an improper .apb file into the 

device, you may damage the Neuron chip in your 
controller. The controller may become unusable.

Neuron ID and Service Pin

To commission a device and add it to a L

ON

W

ORKS

 

network, you need the Neuron ID of the device. There 
are two methods to obtain the Service Pin number.

To locate the Neuron ID number, perform one of the 
following procedures:

1.

Manual entry:

 The Neuron ID address and bar 

code are located on either the top panel of the 
device (surface and DIN rail models), or inside the 
casing of the device (flush mount models).

2.

Service Pin:

 Press the Service Pin on the device 

to broadcast the Neuron ID on the L

ON

W

ORKS

 

network. The Service Pin on the Scheduler is 
located on the bottom right of the device 
(Figure 12). The Display device may have multiple 
methods for broadcasting the Neuron ID over the 
network depending on the revision level of the 
actual controller. The revision number is located on 
the printed circuit board, inside the casing.

Information on Revision levels:

all devices with Revision 5 or later have a 
Service Pin located on the bottom of the device

all devices with Revision 4 or earlier have a 
Reset Pin instead of a Service Pin. (When you 
press the Reset Pin the controller performs a 
cold reset and restarts the device.)

Repair Information

If the LN-Display fails to operate within its 
specifications, replace the unit. For a replacement, 
contact the nearest Johnson Controls® representative.

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.

MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas mettre le système sous tension 
avant d'avoir vérifié tous les raccords de 
câblage. Des fils formant un court-circuit 
ou connectés de façon incorrecte 
risquent d'endommager 
irrémédiablement l'équipement.

Figure 12: Bottom View

Summary of Contents for LN-DSWSC1-0

Page 1: ...terference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to ...

Page 2: ...ox and DIN Rail Figure 2 Flush Mount Casing Dimensions 1 4754 in 37 475 mm 0 1813 in 4 605 mm 6 0000 in 152 4 mm 6 0000 in 152 4 mm 5 4500 in 138 43 mm 5 4500 in 113 03 mm Ø0 1540 in 3 91 mm 4 8086 in 122 13 mm 4 8086 in 122 13 mm 1 1543 in 29 31 mm 0 5000 in 12 7 mm 1 0000 in 25 4 mm 0 0800 in 2 032 mm BACK VIEW BOTTOM VIEW FRONT VIEW SIDE VIEW FIG flush_mount ...

Page 3: ...il the panel clicks into place European Electrical Box Follow the steps in the North American Electrical Box section DIN Rail To mount on a DIN rail 1 Remove the Display panel from the device by gently pressing on the panel and pulling the front panel outward Figure 3 2 Break off the tabs to expose the DIN rail channels in the base plate Figure 5 3 Break off the cover from the exit hole Figure 5 4...

Page 4: ...s 8 Reattach the front panel to the base plate by pressing gently on the display until the panel clicks into place Location Considerations For proper installation and subsequent operation of the Display controller follow these recommendations Allow for proper clearance of device casing wiring terminals and service pin for easy access hardware configuration and maintenance Record the Neuron ID numb...

Page 5: ...ON communication wire is polarity insensitive and can be laid out in either bus star loop or free topology Connect both wires to the NET terminals of the controller If you are inserting multiple wires in the terminals properly twist wires together prior to inserting them in the terminal connectors Figure 11 Note For additional information about network topology and wire length restrictions refer t...

Page 6: ...here are two methods to obtain the Service Pin number To locate the Neuron ID number perform one of the following procedures 1 Manual entry The Neuron ID address and bar code are located on either the top panel of the device surface and DIN rail models or inside the casing of the device flush mount models 2 Service Pin Press the Service Pin on the device to broadcast the Neuron ID on the LONWORKS ...

Page 7: ... length to verify it does not exceed the specifications Wire type Check the wire type to verify it meets the specifications Ensure you are using unshielded wire Network wiring problem Verify the wire connections are correct Absent or incorrect network termination Check the terminations Incorrect or broken terminations make the communication integrity dependent upon a device s position on the netwo...

Page 8: ...8 Kbps Status Indicator Green LEDs on outputs Communication Jack Input 1 8 in 3 5 mm Enclosure Material ABS Resin Color Off White Dimension FMT 6 in x 6 in x 1 48 in 151 x 151 x 38 mm Dimension SMT 4 57 in x 4 57 in x 1 48 in 116 x 116 x 38 mm Shipping Weight FMT 0 88 lb 0 40 kg Liquid Crystal Display LCD Type Backlit Definition 128 x 128 pixels Display Area 2 1 x 2 1 in 53 x 53 mm Screen Saver Cu...