Installation
6-1 Notes for Installation
Important Notices
⚫
Before installation, please contact with local authorized maintenance center, if
unit is not installed by the authorized maintenance center, the malfunction may
not solved, due to discommodious contact.
⚫
The air conditioner must be installed by professionals according to the national
wiring rules and this manual.
⚫
To move and install air conditioner to another place, please contact our local
special service center.
Requirements For Installation Position
⚫
Avoid places of inflammable or explosive gas leakage or where there are strongly
aggressive gases.
⚫
Avoid places subject to strong artificial electric/magnetic fields.
⚫
Avoid places subject to noise and resonance.
⚫
Avoid severe natural conditions (e.g. heavy lampblack, strong sandy wind, direct
sunshine or high temperature heat sources).
⚫
Avoid places within the reach of children.
⚫
Shorten the connection between the indoor and outdoor units.
⚫
Select where it is easy to perform service and repair and where the ventilation
good.
⚫
The outdoor unit shall not be installed in any way that could occupy an aisle,
stairway, exit, fire escape, catwalk or any other public area.
⚫
The outdoor unit shall be installed as far as possible from the doors and windows
of the neighbors as well as the green plants.
Requirements for operations at raised height
⚫
When carrying out installation at 2m or higher above the base level, safety belts
must be worn and ropes of sufficient strength be securely fasten to the outdoor
unit, to prevent falling that could cause personal injury or death as well as
property loss.
Requirements of the mounting structure
⚫
The mounting rack must meet the relevant national or industrial standards in
terms of strength with welding and connection areas rustproofed.
⚫
The mounting rack and its load carry surface shall be able to withstand 4 times or
above the weight of the unit, or 200kg, whichever is heavier.
⚫
The mounting rack of the outdoor unit shall be fastened with expansion bolt.
⚫
Ensure the secure installation regardless of what type of wall on which it is
installed, to prevent potential dropping that could hurt people.
Electrical Safety Requirements
⚫
Be sure to use the rated voltage and air conditioners dedicated circuit for the
power supply, and the power cord diameter must meet the national requirements.
⚫
Be sure to use the rated voltage and air conditioners dedicated
⚫
When the maximum current of air conditioner is ≥16A, it must use the air switch
or leakage protection switch equipped with protection devices.
⚫
The normal operating range is 90%-110% of the local rated voltage.
⚫
The minimum clearance between the air conditioner and the combustibles is 1.5