Johnson Controls IOM2721 Installation Manual Download Page 6

I/O Terminal blocks, ratings, and
requirements

Table 2: I/O terminal blocks, functions, ratings, requirements, and cables

Terminal block label Terminal

label

Function, ratings, requirements

Determine wire size and

maximum cable length

+15 V

15 VDC Power Source

 for active (3-wire) input devices

connected to the Universal IN

n

 terminals.

Provides 100 mA total current

Same as (Universal) 

IN

n

Note: 

Use 3-wire cable for

devices that source power

from the +15 V terminal.

Analog Input - Voltage Mode (0–10 VDC)

10 VDC maximum input voltage
Internal 75k ohm Pull-down

See Guideline 

A

 in Table 3.

Analog Input - Current Mode (4–20 mA)

Internal 100 ohm load impedance

Note: 

A current loop fail-safe jumper can be positioned

to maintain a closed 4 to 20 mA current loop, even when

the power to the expansion module is interrupted or off.

See Guideline 

B

 in Table 3.

Analog Input - Resistive Mode (0–600k ohm)

Internal 12 V. 15k ohm pull up
Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel

[ Johnson Controls sensor], 1k Platinum, and A99B Silicon

Temperature Sensor) Negative Temperature Coefficient (NTC)

Sensor (10k Type L, 10k JCI Type II, 2.252k Type II)

See Guideline 

A

 in Table 3.

IN

n

Binary Input - Dry Contact Maintained Mode

1 second minimum pulse width
Internal 12 V. 15k ohm pull up

See Guideline 

A

 in Table 3.

UNIVERSAL

(Inputs)

ICOM

n

Universal Input Common

 for all Universal Input terminals

Same as (Universal) 

IN

n

Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.

Note: 

The Analog Output (AO) operates in the Voltage

Mode when connected to devices with impedances

greater than 1,000 ohm. Devices that drop below 1,000

ohm may not operate as intended for Voltage Mode

applications.

OUT

n

Analog Output - Current Mode (4–20 mA)

Requires an external load between 0 and 300 ohm.

Note: 

The Analog Output (AO) operates in the Current

Mode when connected to devices with impedances less

than 300 ohm. Devices that exceed 300 ohm may not

operate as intended for Current Mode applications.

ANALOG

(Outputs)

OCOM

n

Analog Output Signal Common

 for all Analog OUT terminals.

See Guideline 

C

 in Table 3.

IOM2721 Input/Output Module Installation Guide

6

Summary of Contents for IOM2721

Page 1: ...equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operatio...

Page 2: ...applications Use shims or washers to mount the expansion module securely and evenly on the mounting surface Mount the expansion module in an area free of corrosive vapors and observe the Ambient Cond...

Page 3: ...or surface in a proper mount position and mark the hole locations through the mounting clips 3 Drill holes in the wall or surface at the marked locations and insert appropriate wall anchors in the ho...

Page 4: ...terminal blocks are mounted on the top of the expansion module SA FC bus terminal block An IOM can be connected to a Sensor Actuator SA bus or a Field Controller FC bus but not to both buses simultan...

Page 5: ...us port RJ 12 modular jack on the front of the expansion module 2 Ensure that the expansion module s device address DIP switches are set to the correct device address See 3 Set DIP switch 128 to ON wh...

Page 6: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Page 7: ...re See Figure 8 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Page 8: ...upply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0 6 mm 22 AWG stranded 4 wire 2...

Page 9: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Interna...

Page 10: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Page 11: ...pansion module on the bus You set an expansion module s device address by setting the positions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 12...

Page 12: ...e on Descriptions 0 Switch 128 Off Reserved for FC Bus Supervisory Controller not for use on controllers or expansion modules 1 3 Switch 128 Off Reserved for peripheral devices not for use on controll...

Page 13: ...er to the expansion module is interrupted or off Figure 12 Current loop jumper positions Setting the current loop jumper to the Enabled position Figure 12 connects an internal 100 ohm resistor across...

Page 14: ...tartup in progress not ready for normal operation SA FC BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady No Data Transmission N A auto baud not supported On Steady Com...

Page 15: ...k of 10 Note These terminal blocks can be used as replacement parts if keeping consistent terminal block colors is important AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of...

Page 16: ...w Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module Housing Enclosure material ABS and...

Page 17: ...C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 5...

Page 18: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: