118
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
AWACS™ Applications
Pre-Alarm
D.2.5 Cooperative Multi-Detector Sensing
Cooperative Multi-Detector Sensing is the ability of a smoke detector to consider readings from
nearby detectors in making alarm or pre-alarm decisions. Each detector can include up to two other
detectors in its decision. Without statistical sacrifice in the ability to resist false alarms, Cooperative
Multi-Detector Sensing allows a detector to increase its sensitivity to actual smoke by a factor of
almost 2 to 1. Ion, photo and laser detector types can participate. Cooperative Multi-Detector
Sensing also allows the combination of ionization with photoelectric technology in reaching an
alarm decision. The figure below shows a graph representing Cooperative Multi-Detector Sensing:
Figure D.5 Cooperative Multi-Detector Sensing
D.3 Pre-Alarm
D.3.1 Definition
The Pre-Alarm function is a programmable option which determines the system’s response to real-
time detector sensing values above the programmed setting. Use the Pre-Alarm function to get an
early warning of incipient or potential fire conditions. There are two levels of Pre-Alarm:
• Alert (Refer to “Alert Level” below)
• Action (Refer to “Action Level” on page 119)
Alert and Action Pre-Alarm settings are set with point programming. Unique Pre-Alarm sensitivity
levels (PA) for individual detectors are listed in “Detector Sensitivity Settings” on page 119.
The LEDs on detectors polled in FlashScan mode will light steady green when in pre-alarm.
D.3.2 Alert Level
Alert Functions
The control panel software, in addition to checking for alarm levels, checks for Pre-Alarm
thresholds for each addressable, intelligent smoke detector programmed for Pre-Alarm. If a
detector’s real-time sensing level exceeds the programmed Alert threshold, the control panel
indicates a Pre-Alarm condition for the detector. The control panel does the following functions
when a detector reaches pre-alarm level:
• The Pre-Alarm message is sent to the History buffer and to installed printers. The message
is sent (and time stamped) at the time that it first occurred. This historical data could provide
valuable information about the progress of a fire.
• The
PRE
-
ALARM
LED flashes and the panel sounder pulses until acknowledged.
• Zone Z000 (general alarm) or any other zone and the System Trouble and System Alarm
relays do not activate.
SMOKE
OBSCURA
T
ION
Time (minutes)
Alarm
Combined
3 Sensors
Awacs5a.
cdr
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...