102
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Releasing Applications
Abort Switches
How to Program a Manual Release Delay Switch
The following contains information needed to program a Manual Release Delay switch for a
monitor module.
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier
NBG-12LRA)—used to initiate a manual release with 10-second delay time.
A Manual Release Delay switch overrides the FACP programmed Delay Time, but not
Soak Time.
Multiple monitor modules can be programmed with a
MAN
REL
DELAY
type code. They
work like multiple conventional manual release switches on a conventional zone.
Program
Select a monitor module for the manual release function. While programming this module
(refer to “Module Point” on page 43 for instructions),
1.
Select the
MAN
REL
DELAY
type code.
2.
Enter the number of the desired releasing zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example
A programming example of a Monitor module programmed for
MAN
REL
DELAY
switch
for Releasing Zone ZR05.
Figure B.11 Monitor Module Configured as a Manual Release Delay Switch
For example, program releasing zone ZR05 with a Manual Release Delay switch for the following
releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = NO, Soak Time = 30.
When the Manual Release Delay Switch activates, the control panel replaces the remainder of the
15-second Delay Time, if running, with a 10-second timer.
Examples:
1.
The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP delay timer has counted down to 12 seconds. The 12
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 13 seconds, less than the original 15 second FACP Delay Timer countdown.
SYSTEM
NORMAL
SYSTEM
ACT IVATED
Detector
ZR05
NBG-12LRA
station with
Manual Release
Lever
Monitor
Module
Type Code
MAN REL DELAY
SLC
output
module
SLC
output
module
Summary of Contents for IFC-3030
Page 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Page 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Page 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Page 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Page 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Page 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Page 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Page 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Page 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Page 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...