Section 5: Programming
13
–
2-Way Audio Attribute
ON: Panel is able to initiate a 2 way audio session.
OFF: Only the microphone turns on, initiating a a Listen-in only session. The speaker remains off.
14
–
Hold Up Verification
ON: An alarm from zones of this type can contribute to a verified hold up alarm. Use this attribute with Panic and Hold Up zones.
OFF: An alarm from zones of this type does not contribute to a verified hold up alarm. The zone does not cause the hold up verification timer to start
counting down, or generate a verified hold up if the alarm is detected while the timer is running.
15 - Triple EOL
ON: The zone requires triple-end-of-line resistors.
OFF: The zone follows programming in section [013] option 2.
EOL resistance
This section describes how to program EOL resistances to custom values.
[004] End of line resistance
Use this menu to program custom resistance values for SEOL, DEOL, and TEOL options in 3-digit format. For example, to
program the value of 0.5 kΩ, enter 005.
[001] – Single EOL
Alarm
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 28 kΩ (005 to 280)
[002] – Double EOL
Alarm
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 15 kΩ (005 -150)
Tamper
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 15 kΩ (005 -150)
[003] – Triple EOL
Alarm
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 7.5 kΩ (005 -075)
Tamper
Default value: 5.6 kΩ
Programmable range: 0.5 kΩ to 7.5 kΩ (005 -075)
Fault/Mask
Default value: 10 kΩ
Programmable range: 0.5 kΩ to 15 kΩ (005 -150)
System times
This section describes how to program various timers applicable to the entire alarm system.
[005] System times
This is the base menu used by installers to program timers, including system area [000], partition timers [001]-[008], and day-
light saving time [901]/[902].
[000] – System Area
Bell Cutoff Time
System sirens follow this timer. Fire alarms follow this timer if section [014] option 8 (Fire Bell Continues Option) is off. System tampers follow this
timer. The bell cutoff time is programmed in minutes. Valid entries are 001 to 255 minutes.