Section 2: Installation
2.3 General wiring instructions
To connect the wiring for the PowerSeries Pro, complete the following steps:
1. Ensure all wires are secured to the enclosure using cable ties. See figure 2-8 to figure 2-14 for locations.
2. Route the AC line into the enclosure through the provided opening, as indicated in figure 2-8.
3. Route the DC wires to the alarm controller as shown. Use cable ties to secure the DC wires to the enclosure.
4. Route wiring for modules and other devices into the enclosure through provided openings. Remove knockouts as
required.
Note:
For HSC3030CAR attack-resistant enclosure, all unused holes must be covered by plastic plugs (shipped with cab-
inet).
This diagram shows routing of power limited and non-power limited wiring inside the enclosure. Battery leads and AC cord
are non-power limited. All other wiring is power limited.
Figure 2-9 Panel wiring for HSC3010C
For HSC3010C installations, complete the following steps:
1. If mounting the power supply inside the cabinet, attach it as per figure 2-4 using supplied hardware. Use cable ties to
secure the DC wires to the enclosure.
IMPORTANT!
Minimum 1/4-inch (6.4 mm) separation must be maintained at all points between battery/AC wiring and all other wiring con-
nections. Do NOT route any wiring over circuit boards. Maintain at least 1 inch (25.4 mm) separation.
2. Install the grommet strip (available separately – p/n 57000933) into the opening on back of cabinet as indicated in figure
2-4. Route the AC cable out of the enclosure through the opening indicated in the diagram.
3. If mounting the power supply outside the enclosure, attach it to the wall using suitable hardware. Route DC wires into the
enclosure and secure them with cable ties. See figure 2-4 for approved wire length/gauge.
Note:
For ULC commercial Fire applications, use enclosure model HSC3010CR.
- 17 -