Section 6: Programming Worksheets
056
24 Hour High Temperature
ü
ü
ü
CP-01
ü
CP-01
ü
057
24 Hour Low Temperature
ü
ü
ü
CP-01
ü
CP-01
ü
060
24-Hr Non-Latching Tamper
ü
ü
CP-01
ü
CP-01
ü
061
24-Hr Anti-Masking
ü
066
Momentary Keyswitch Arm
ü
067
Maintained Keyswitch Arm
ü
068
Momentary Keyswitch Disarm
ü
069
Maintained Keyswitch Disarm
ü
071
Door Bell
ü
ü
072
Push to Set
ü
6.3 End Of Line Resistance
[004] End of Line Resistance
Description
on page 84
001 – Single EOL
Alarm (Default 5.6 kΩ)
Valid range: 0.5 kΩ to 28 kΩ (005 to 280)
002 – Double EOL
Alarm (Default 5.6 kΩ)
Valid range: 0.5 kΩ to 15 kΩ (005 -150)
Tamper (Default 5.6 kΩ)
Valid range: 0.5 kΩ to 15 kΩ (005 -150)
003 –Triple EOL
Alarm (Default 5.6 kΩ)
Valid range: 0.5 kΩ to 7.5 kΩ (005 -075)
Tamper (Default 5.6 kΩ)
Valid range: 0.5 kΩ to 7.5 kΩ (005 -075)
6.4 System Times
[005] System Times
000 – System Area
Bell Cutoff (Default: 004 minutes):
Description
on page 84
(3-Digit Decimal)
Bell Delay Time (Default: 000 minutes):
Burglary Verification Timer (Default: 060 minutes):
Holdup Verification Timer (Default: 008 hours):
Zone Loop Response Time (Default: 025 x 10 ms):
Automatic Clock Adjust (Default: 060 seconds):
001 – Partition 1 Timer
Entry Delay 1 (Default: 030):
Entry Delay 2 (Default: 045):
Exit Delay (Default: 120):
Settle Delay (Default: 010):
002 – Partition 2 Timer
Entry Delay 1:
See partition 1 for defaults
Entry Delay 2:
- 162 -