background image

7

4.2  Installation Position

1.  Horizontal Installation 

Locate the “Y” union pipe section on the same horizontal plane. (Inclination within 30

o

Make the straight section a minimum of 1.6ft (0.5m) after the vertical bend.

2.  Vertical Installation 

Straight section of the pipe connection on the outdoor unit side is made as follows:
a)  The collective pipe connection part is installed upward; the straight section must be a minimum of 1.6ft (0.5m).
b)  The collective pipe connection part is installed downward; the straight section must be a minimum of 1.6ft 

(0.5m).

3.  Piping from Multi-Kit to Indoor Unit

Upward

Downward

Horizontally

Total Straight Section

Min. 1.6ft (0.5m)

Inclination
within 30

o

30

o

A

Inclination

(View from A)

INCORRECT

Total Straight Section
Min. 1.6ft (0.5m)

Total Straight Section
Min. 1.6ft (0.5m)

Upward

Downward

Outdoor Unit

Outdoor Unit

Multi-Kit

Example: Recommended From each Indoor Unit to Multi-Kit, use hard copper pipes that bend to prevent kinking.

Bending Pipe

Connection Pipe 

Example: Not Recommended

Indoor Unit

Straight piping does not allow for movement of the piping when it expands
or contracts. 

Hard Copper Piping will expand and contract due
to temperature changes in piping.

Hard Copper Piping will expand and contract due to
temperature changes in piping.

NOTICE:

[ Fixing for Liquid Piping and Gas Piping ]

Multi-Kit

Install Horizontally

NOTICE:

Gas Piping

Installing Part for Piping 

Liquid Piping

When on-site piping is installed using
soft or hard copper, make sure that the
piping is installed to allow for movement
of the piping. Temperature changes cause
contraction

 

and expansion of the piping.

Due to the properties of hard copper piping,
expansion and contraction take place during
seasons of heat and cold. Do not strap gas
refrigerant and piping containing liquids together
as kinks. 

Summary of Contents for Hitachi MW-NP282A3

Page 1: ... manual may be reproduced in any way without the expressed written consent of Johnson Controls Hitachi Air Conditioning Ɣ This heat pump air conditioning unit will be operated and serviced in the United States of America and comes with a full complement of the appropriate Safety Danger and Caution warnings Ɣ If you have questions please contact your distributor or dealer Ɣ This manual provides com...

Page 2: ...inside the indoor or outdoor units All safety features disengagement and interlocks must be in place and functioning correctly before the equipment is put into operation If these devices are improperly adjusted or tampered with in any way a serious accident can occur Never bypass or jump out any safety device or switch Ɣ Johnson Controls Hitachi Air Conditioning will not assume any liability for i...

Page 3: ... DLU EDႉH ƕ A snowy area Install the outdoor unit on a raised platform that is higher than drifting snow Provide snow vents Ɣ R QRW LQVWDOO WKH XQLW LQ WKH IROORZLQJ SODFHV RLQJ VR FDQ UHVXOW LQ DQ H SORVLRQ UH GHIRUPDWLRQ FRUURVLRQ RU product failure ƕ SORVLYH RU ÀDPPDEOH DWPRVSKHUH ƕ KHUH D UH RLO VWHDP RU SRZGHU FDQ GLUHFWO HQWHU WKH XQLW VXFK DV QHDUE RU DERYH D NLWFKHQ VWRYH ƕ Where oil inclu...

Page 4: ... WKH XQLW V intended home country or market Johnson Controls Hitachi Air Conditioning distributors similarly are only authorized to provide refrigerants that have been approved for use in the countries or markets they serve The UHIULJHUDQW XVHG LQ WKLV XQLW LV LGHQWL HG RQ WKH XQLW V IDFHSODWH DQG RU LQ WKH DVVRFLDWHG PDQXDOV Q DGGLWLRQV RI UHIULJHUDQW LQWR WKLV XQLW PXVW FRPSO ZLWK WKH FRXQWU V U...

Page 5: ...door or outdoor units without turning OFF the main power supply Ɣ IWHU VWRSSLQJ RSHUDWLRQ EH VXUH WR ZDLW DW OHDVW YH PLQXWHV EHIRUH WXUQLQJ Rႇ WKH PDLQ SRZHU VZLWFK Otherwise water leakage or electrical breakdown may result Disconnect the power supply completely before attempting any maintenance for electrical parts Check to ensure that no residual voltage is present after disconnecting the power...

Page 6: ... Outdoor Unit To Indoor Unit To Main Piping ID 1 2 ID 1 4 ID 3 8 ID 3 8 ID 1 2 ID 1 2 To Outdoor Unit To Indoor Unit To Main Piping OD 1 1 8 ID 1 ID 5 8 ID 7 8 ID 3 4 ID 1 2 ID 3 8 OD 1 4 ID 5 8 OD 1 2 MW NP692A3 ID 1 2 ID 5 8 ID 1 1 8 ID 1 1 8 ID 1 ID 3 4 ID 7 8 ID 7 8 To Outdoor Unit To Indoor Unit To Main Piping ID 3 8 ID 3 4 ID 5 8 ID 1 2 ID 3 8 ID 1 2 ID 5 8 ID 5 8 ID 7 8 ID 1 4 To Outdoor Un...

Page 7: ...ard Downward Outdoor Unit Outdoor Unit Multi Kit Example Recommended From each Indoor Unit to Multi Kit use hard copper pipes that bend to prevent kinking Bending Pipe Connection Pipe Example Not Recommended Indoor Unit Straight piping does not allow for movement of the piping when it expands or contracts Hard Copper Piping will expand and contract due to temperature changes in piping Hard Copper ...

Page 8: ...W 3LSLQJ When installing pipe through the wall secure a cap at the end of the pipe Attach a cap or vinyl tape INCORRECT CORRECT INCORRECT CORRECT Do NOT place the pipe directly on the ground In case of rain attach a cap or put a plastic bag over the pipe end Attach a cap or vinyl tape INCORRECT CORRECT Attach a cap or plastic bag with rubber band Hole Rain water can enter inch mm Diameter A Min In...

Page 9: ...ld supplied insulation There should be no gaps showing After installation it is recommended that the customer retain this manual for future reference Ɣ 3HUIRUP LQVXODWLRQ ZRUN RQO ZKHQ WKH VXUIDFH WHPSHUDWXUH RI WKH SLSH PDWHULDO KDV FRROHG WR URRP temperature Anything done immediately after brazing can cause the insulation to melt Ɣ XULQJ SLSLQJ ZRUN DOZD V FRYHU RYHU RU SOXJ WKH RSHQ HQG WR NHHS...

Page 10: ......

Page 11: ......

Page 12: ...P5416959 rev 2 2017 Hitachi Johnson Controls Air Conditioning Inc Code No LIT 1202411 Revised January 2020 ...

Reviews: