Table 2: GS3000 Gas Detection Sensor Series setup menu
Specification
Requirements
Description
CO range
Only if you install the CO sensor and the
output type is voltage or mA
The factory default CO range is 0 ppm to
300ppm. You can change the CO sensing
range and output scale to 0 ppm to 100
ppm, 0 ppm to 150 ppm, 0 ppm to 300 pm, 0
ppm to 400 ppm, or 0 ppm to 500 ppm.
Temperature
Only if the temperature sensor output type
is voltage or mA
The factory default temperature range
is -20°C to 50°C. You can change the
temperature sensing range and output scale
to -4°F to 122°F, 32°F to 122°F, -20°C to 50°C,
or 0°C to 50°C.
Buzzer
The factory default setting is enable. Use the
UP
or
DOWN
buttons to enable or disable
the buzzer alarm. When disabled, the buzzer
does not sound if the buzzer trip point is
exceeded. The buzzer still beeps on start-up
and still beeps for a fault alarm, if enabled,
and ReCal alarm, if enabled.
CO buzzer trip point
The factory default setting for the CO buzzer
alarm trip point is 150 ppm. You can set
the buzzer alarm trip point for CO to OFF
or from 20 ppm to 500 ppm in 10 ppm
increments. The buzzer may operate as a
CO alarm, an NO
2
alarm or both, depending
on the trip point settings. If set to OFF, the
CO buzzer alarm does not operate as a CO
alarm.
CO buzzer delay
Only if you install the CO sensor
The factory default setting for the CO buzzer
delay is 5 min. You can set the CO buzzer
delay from 0 to 10 min in 1 min increments.
This is only available if the CO buzzer trip is
enabled, and not set to OFF.
NO
2
buzzer trip point
The factory default setting for the NO
2
buzzer trip point is 2 ppm. The buzzer alarm
trip point for NO
2
may be set to OFF, or from
1 ppm to 10 ppm in 1 ppm increments.
The buzzer may operate as a CO alarm, an
NO
2
alarm or both, depending on the trip
point settings. If set to OFF, the buzzer does
not operate as an NO
2
alarm.
NO
2
buzzer trip delay
Only if you install the NO
2
sensor
The factory default setting for the NO
2
buzzer delay is 5 min. The NO
2
buzzer delay
may be set from 0 min to 10 min in 1 min
increments.
Buzzer
Press the
UP
or
DOWN
button to toggle the
buzzer ON or OFF.
Strobe
The factory default setting is enable. Use the
UP
or
DOWN
buttons to enable or disable
the strobe LED. When disabled, the strobe
does not flash if the strobe trip point is
exceeded. The strobe still flashes on start-up
and still flashes for a fault alarm, if enabled.
GS3000 Gas Detection Sensor Series Installation Guide
8