Johnson Controls Unitary Products

833101-UTD-B-0612

TABULAR DATA SHEET

Outdoor Split System Air Conditioner 1.5 Thru 5 Tons

MODELS: GCGD18* THRU 60

13 SEER – R-22 – 1 PHASE

All dimensions are in inches. They are subject to change without notice. 
Certified dimensions will be provided upon request.

.

Physical and Electrical Data

MODEL

GCGD18S

21S2X(E)

GCGD24S

21S2X(E)

GCGD30S

21S2(E)

GCGD36S

21S2(E)

GCGD42S

21S2(E)

GCGD48S

21S2(E)

GCGD60S

21S2(E)

Unit Supply Voltage

208-230V, 1



 60Hz

Normal Voltage Range 

1

187 to 252

Minimum Circuit Ampacity

8.5

13.2

14.0

18.2

19.9

22.7

33.5

Max. Overcurrent Device Amps 

2

15

20

20

30

30

35

50

Min. Overcurrent Device Amps 

3

15

15

15

20

25

25

35

Compressor Type 

Recip

Recip

Recip

Recip

Recip

Recip

Scroll

Compressor Amps

Rated Load

6.4

9.9

10.6

13.4

14.7

17.0

25.6

Locked  Rotor

36

54

61

78

78

86

150

Crankcase Heater

No

No

No

No

No

No

No

Factory External Discharge Muffler

No

No

Yes

Yes

Yes

Yes

No

Factory External Check Valve

No

No

No

No

No

No

No

HS Kit Required with TXV 

4

Yes

Yes

Yes

Yes

Yes

Yes

No

Fan Motor Amps

Rated Load

0.5

0.8

0.80

1.4

1.5

1.5

1.5

Fan Diameter Inches

18

18

18

18

22

22

22

Fan Motor

Rated HP

1/12

1/8

1/8

1/4

1/4

1/4

1/4

Nominal RPM

1100

1075

1075

1100

850

850

850

Nominal CFM

1550

1850

1950

2400

3000

3000

3300

Coil

Face Area Sq. Ft.

9.60

9.60

11.30

12.10

16.50

16.50

19.75

Rows  Deep

1

1

1

1

1

1

1

Fin / Inches

23

23

23

23

23

23

23

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

5/8

3/4

3/4

3/4

7/8

7/8

1-1/8

Unit Charge (Lbs. - Oz.) 

5

See Note 5 Below

Charge Per Foot, Oz.

0.66

0.68

0.68

0.68

0.70

0.70

0.76

Operating Weight Lbs.

130

130

150

160

175

176

200

Models with “E” on the end of the model number have an ElectroFin® coating on the outdoor coil.

1. Rated in accordance with AHRI Standard 110-2012, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model. 
5. Units have been shipped without refrigerant.  Remove nitrogen holding charge, evacuate, and charge to the system charge listed on the second page of the data 

sheet.  System charges listed include 15 feet of lineset.

B

C

A

Unit

Model

Dimensions

(Inches)

Refrigerant Connection

Service Valve Size

A

1

1. Overall height from bottom of base pan to top of fan guard.

B

C

Liquid

Vapor

18

28

23-1/2

23-1/2

3/8”

3/4”

24

28

23-1/2

23-1/2

30

32

23-1/2

23-1/2

36

34

23-1/2

23-1/2

42

34

29

29

7/8”

48

34

29

29

60

40

29

29

7/8”

2

2. Adapter fitting required for 1-1/8” line set.