Important:
Connect 24 VAC supply power to the
controller and all other network devices so
that transformer phasing is uniform across
the network devices. Powering network
devices with uniform 24 VAC supply power
phasing reduces noise, interference, and
ground loop problems. The controller does
not require an earth ground connection.
Wireless Network Applications
The controller can also be installed in a wireless
application using an FX-ZFR1811 Wireless Field Bus
Router.
To configure a controller for use with the FX-ZFR Series
Wireless Field Bus system:
Note:
FX-PCXs can talk wirelessly on the FC bus only.
1. Connect the FX-ZFR1811 Wireless Field Bus Router
to the FC bus port (RJ-12 modular jack) on the front
of the controller.
2. Ensure that the controller's device address DIP
switches are set to the correct device address. See
3. Set DIP switch 128 to ON, which enables wireless
operation on the controller.
For more information on installing a controller in a
wireless configuration, refer to the
FX-ZFR1811
Wireless Field Bus Router Installation Instructions
(Part No. 24-10325-29)
.
Termination Details
A set of Johnson Controls
®
termination diagrams provides details for wiring inputs and outputs to the controllers.
See the figures in this section for the applicable termination diagrams.
Table 2: Termination Details
Termination Diagrams
Type of
Input/Output
Type of Field Device
UI
Temperature Sensor
UI
Voltage Input - External
Source
UI
Voltage Input - Internal Source
6
FX-PCX47 Expansion Input/Output Module Installation Instructions