Johnson Controls FX-PCX47 Installation Instructions Manual Download Page 5

Figure 5: SA Bus Terminal Block Wiring

Note:

The SA PWR/SHLD terminal does not supply 15
VDC. The SA PWR/SHLD terminal is isolated and
can be used to connect (daisy chain) the 15 VDC
power leads on the SA bus (

Figure 5

) or the cable

shields on the FC bus (

Figure 4

).

The SA bus supervisor supplies 15 VDC to
devices on the SA bus requiring power.

SA/FC Bus Port

The SA/FC bus port on the front of the controller is an
RJ-12, 6-position modular jack that provides a connection
for devices on the SA bus, a Bluetooth Commissioning
Converter, ZigBee

®

wireless dongle, or an FX-ZFR1811

Wireless Router (depending on which bus the FX-PCX
is operating on).

The SA/FC bus port is connected internally to the SA/FC
bus terminal block. See

Table 5

for more information.

The SA/FC bus port pin assignment is shown in

Figure

6

.

Figure 6: Pin Number Assignments for Sensor, SA

Bus and FC Bus Ports on Controllers

Supply Power Terminal Block

The 24 VAC supply power terminal block is a gray,
removable, 3-terminal plug that fits into a board-mounted
jack on the top right of the controller.

Wire the 24 VAC supply power wires from the transformer
to the HOT and COM terminals on the terminal plug as
shown in

Figure 7

. The middle terminal on the supply

power terminal block is not used. See

Table 5

for more

information about the supply terminal block.

Figure 7: 24 VAC Supply Power Terminal Block Wiring

Note:

The supply power wire colors may be different on
transformers from other manufacturers. Refer to
the transformer manufacturer’s instructions and
the project installation drawings for wiring details.

Important:

Connect 24 VAC supply power to the
controller and all other network devices so
that transformer phasing is uniform across
the network devices. Powering network
devices with uniform 24 VAC supply power
phasing reduces noise, interference, and
ground loop problems. The controller does
not require an earth ground connection.

Wireless Network Applications

The controller can also be installed in a wireless
application using an FX-ZFR1811 Wireless Field Bus
Router.

To configure a controller for use with the FX-ZFR Series
Wireless Field Bus system:

Note:

FX-PCXs can talk wirelessly on the FC bus only.

5

FX-PCX47 Expansion Input/Output Module Installation Instructions

Summary of Contents for FX-PCX47

Page 1: ...nstalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in w...

Page 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remov...

Page 3: ...le 5 6 Cover Lift Tab One of Two See Removing the Controller Cover 7 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See Table 5 8 Binary Input BI Terminal Block 2 Binary Inputs See T...

Page 4: ...figuring and wiring an MS TP Bus FC bus and SA bus refer to the FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 or MS TP Communications Bus for BCM System Technical B...

Page 5: ...on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 The middle terminal on the supply powe...

Page 6: ...o the FX ZFR1811 Wireless Field Bus Router Installation Instructions Part No 24 10325 29 Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outpu...

Page 7: ...rrent Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI or BI Dry Contact Binary Input CO or AO 0 20 VDC Output...

Page 8: ...CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO 4 20 mA Output to Actuator CO or AO 4 20 mA Output to Actuator AO Voltage Analog Output AO Analog Output Current CO 24 VAC Triac Output Sw...

Page 9: ...24 VAC Triac Output Switch High Externally Sourced CO Incremental Control to Actuator Switch High Externally Sourced BO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary...

Page 10: ...e BO Incremental Control to Actuator Switch High Externally Sourced SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Termin...

Page 11: ...rminal Label Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal 15 VDC Power Source for active 3 wire input devices connected to the U...

Page 12: ...greater than 1 000 ohm Devices that drop below 1 000 ohm may not operate as intended for Voltage Mode applications OUTn ANALOG Outputs Analog Output Current Mode 4 20 mA Requires and external load be...

Page 13: ...imum output voltage 10 mA maximum output current Required an external load of 1 000 ohm or more OUTn CONFIGURABLE Outputs See Guideline C in Table 4 Binary Output 24 VAC Triac External Power Source on...

Page 14: ...per 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 229 m 750 ft twisted wi...

Page 15: ...cable recommended Note On the SA Bus the and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC or SA Bus Communications FC BUS 2 or SA BUS 2 Signal Reference Co...

Page 16: ...itch 4 ON followed by switch 1 16 4 1 21 See Figure 9 3 Set switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC bus applications ensur...

Page 17: ...under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the...

Page 18: ...Jumpers The current loop fail safe jumpers are on the circuit board under the controller cover near the UI terminals Figure 10 When a UI is defined in the system software as a 4 20 mA Analog Input and...

Page 19: ...For a replacement controller contact your Johnson Controls representative Accessories See Table 9 for controller accessories ordering information Table 9 Accessories Ordering Information Description...

Page 20: ...FX PCG FX PCA FX PCX and FX PCV field controllers Also allows use of the FX ZFR Checkout Tool FX ZCT in FX PCT Note The ZFR USBHA 0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle For additional inf...

Page 21: ...28 KB Random Access Memory RAM Memory 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mod...

Page 22: ...erformance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls I...

Reviews: