Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements

Input and Output Wiring Guidelines

Table 3

provides information and guidelines about the

functions, ratings, and requirements for the controller
input and output terminals; and references guidelines for
determining proper wire sizes and cable lengths.

In addition to the wiring guidelines in

Table 3

, observe

these guidelines when wiring controller inputs and
outputs:

Run

all

low-voltage wiring and cables separate from

high-voltage wiring.

All input and output cables, regardless of wire size or
number of wires, should consist of stranded, insulated,
and twisted copper wires.

Shielded cable is not required for input or output
cables.

Shielded cable is recommended for input and output
cables that are exposed to high electromagnetic or
radio frequency noise.

Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software setup.
Cable runs over 30 m (100 ft) may require an offset
in the input/output software setup.

Table 3: FX-PCX47 Terminal Blocks, Functions, Ratings, Requirements, and Cables

Determine Wire Size and

Maximum Cable Length

1

Function, Ratings, Requirements

Terminal
Label

Terminal Block
Label

Same as (Universal)

INn

Note:

Use 3-wire cable for

devices that source power from
the +15V terminal.

15 VDC Power Source

for active (3-wire) input devices

connected to the Universal IN

n

terminals.

Provides 100 mA total current

+15 V

UNIVERSAL

(Inputs)

See Guideline

A

in

Table 4

.

Analog Input - Voltage Mode (0–10 VDC)

10 VDC maximum input voltage

Internal 75k ohm Pull-down

INn

See Guideline

B

in

Table 4

.

Analog Input - Current Mode (4–20 mA)

Internal 100 ohm load impedance

Note:

A current loop fail-safe jumper can be positioned to

maintain a closed 4 to 20 mA current loop, even when the
power to the controller is interrupted or off. See

UI Current

Loop Jumpers

.

See Guideline

A

in

Table 4

.

Analog Input - Resistive Mode (0–600k ohm)

Internal 12 V. 15k ohm pull up

Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[Johnson Controls

®

sensor], 1k Platinum, and A99B Silicon

Temperature Sensor) Negative Temperature Coefficient
(NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k Type
II)

See Guideline

A

in

Table 4

.

Binary Input - Dry Contact Maintained Mode

1 second minimum pulse width

Internal 12 V. 15k ohm pull up

Same as (Universal)

INn

Universal Input Common

for all Universal Input terminals

Note:

All Universal ICOM

n

terminals share a common,

which is isolated from all other commons.

ICOMn

11

FX-PCX47 Expansion Input/Output Module Installation Instructions

Summary of Contents for FX-PCX47

Page 1: ...nstalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in w...

Page 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remov...

Page 3: ...le 5 6 Cover Lift Tab One of Two See Removing the Controller Cover 7 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See Table 5 8 Binary Input BI Terminal Block 2 Binary Inputs See T...

Page 4: ...figuring and wiring an MS TP Bus FC bus and SA bus refer to the FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 or MS TP Communications Bus for BCM System Technical B...

Page 5: ...on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 The middle terminal on the supply powe...

Page 6: ...o the FX ZFR1811 Wireless Field Bus Router Installation Instructions Part No 24 10325 29 Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outpu...

Page 7: ...rrent Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI or BI Dry Contact Binary Input CO or AO 0 20 VDC Output...

Page 8: ...CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO 4 20 mA Output to Actuator CO or AO 4 20 mA Output to Actuator AO Voltage Analog Output AO Analog Output Current CO 24 VAC Triac Output Sw...

Page 9: ...24 VAC Triac Output Switch High Externally Sourced CO Incremental Control to Actuator Switch High Externally Sourced BO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary...

Page 10: ...e BO Incremental Control to Actuator Switch High Externally Sourced SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Termin...

Page 11: ...rminal Label Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal 15 VDC Power Source for active 3 wire input devices connected to the U...

Page 12: ...greater than 1 000 ohm Devices that drop below 1 000 ohm may not operate as intended for Voltage Mode applications OUTn ANALOG Outputs Analog Output Current Mode 4 20 mA Requires and external load be...

Page 13: ...imum output voltage 10 mA maximum output current Required an external load of 1 000 ohm or more OUTn CONFIGURABLE Outputs See Guideline C in Table 4 Binary Output 24 VAC Triac External Power Source on...

Page 14: ...per 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 229 m 750 ft twisted wi...

Page 15: ...cable recommended Note On the SA Bus the and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC or SA Bus Communications FC BUS 2 or SA BUS 2 Signal Reference Co...

Page 16: ...itch 4 ON followed by switch 1 16 4 1 21 See Figure 9 3 Set switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC bus applications ensur...

Page 17: ...under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the...

Page 18: ...Jumpers The current loop fail safe jumpers are on the circuit board under the controller cover near the UI terminals Figure 10 When a UI is defined in the system software as a 4 20 mA Analog Input and...

Page 19: ...For a replacement controller contact your Johnson Controls representative Accessories See Table 9 for controller accessories ordering information Table 9 Accessories Ordering Information Description...

Page 20: ...FX PCG FX PCA FX PCX and FX PCV field controllers Also allows use of the FX ZFR Checkout Tool FX ZCT in FX PCT Note The ZFR USBHA 0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle For additional inf...

Page 21: ...28 KB Random Access Memory RAM Memory 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mod...

Page 22: ...erformance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls I...

Reviews: