Table 8: FX-PCV18 Controller accessories. Order separately
Product Code Number Description
Mobile Access portal
(MAP) Gateway
To identify the appropriate product for your region, refer to the
Mobile
Access Portal Gateway Catalog Page
(LIT-1900869).
1
NS Series Network
Sensors
Refer to the
NS Series Network Sensors Product Bulletin (LIT-12011574)
for
specific sensor model descriptions.
Y64T15-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot
Mount, 30 in. Primary Leads and 30 in. Secondary Leads, Class 2
Y65A13-0
Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount
(Y65AS), 8 in. Primary Leads and 30 in. Secondary Leads, Class 2
Y65T42-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub
Mount (Y65SP+), 8 in. Primary Leads and Secondary Screw Terminals,
Class 2
Y65T31-0
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot
Mount (Y65AR+), 8 in. Primary Leads and Secondary Screw Terminals,
Class 2
AP-TBK4FC-0
Replacement MS/TP FC Bus Terminal, 4-Position Connector, Blue, Bulk
Pack (10 pack)
AS-CBLTSTAT-0
AS-CBLTSTAT-0 Cable adapter for connection to 8-pin TE-6700 Series
sensors
AS-CBLVMA-1
Cable Adapter, 8-pin Female Socket to 6-Pin Male Jack (Bulk Pack of 10)
AS-CBLVMA-2
Cable Adapter, 8-pin Female Socket to 8-pin Male Jack with 6-Pin Female
Socket for Wireless Commissioning Converter (Bulk Pack of 10)
NS-WALLPLATE-0
Network Sensor Wall Plate (80 mm x 80 mm [3.15 in. x 3.15 in.] square),
used with an 80 mm by 80 mm (3.15 in. x 3.15 in.) network sensor and
must be mounted to a 0.6 m by 1.2 m (2 ft by 4 ft) wall box
1
The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be
supported on select controllers.
Technical specifications
Table 9: FX-PCV18 Controllers
Product Code Numbers
FX-PCV1832-1:
Programmable VAV Box N2 Controller for cooling only
and cooling with reheat and fan control applications
FX-PCV1826-1:
Same as above except with no differential pressure
sensor
Supply Voltage
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz,
Power Supply Class 2 (North America), Safety Extra-Low Voltage
(SELV) (Europe)
Power Consumption
10 VA typical, 14 VA maximum
Note:
The VA rating does not include any power supplied to
the peripheral devices connected to Binary Outputs (BOs) or
Configurable Outputs (COs), which can consume up to 12 VA for
each BO or CO, for a possible total consumption of an additional
60 VA (maximum).
27
FX-PCV1826/1832 Programmable VAV Box Controller Installation Instructions