Troubleshooting
Table 7 provides LED status indicator information for troubleshooting the FX-PCV18 controller.
Note:
If you experience short circuits in the 24 VAC power supply causing protective devices
such as breakers or fuses to trip, make sure that the power connections on the VMA are not
reversed. The most common cause of this problem is when the 24 VAC power supply on the
PCV is reversed but not reversed on a connected secondary device. Improper wiring of this
power terminal may cause a short circuit across the 24 VAC power supply on -1 models.
Repair information
If the FX-PCV18 Series controller fails to operate within its specifications, replace the unit. For a
replacement unit, contact the nearest Johnson Controls representative.
LED and accessories tables
Table 7: FX-PCV18 Controller status LEDs
LED label
LED color
Normal state Descriptions of LED states
POWER
Green
On Steady
Off Steady = No power
On Steady = Power is supplied by primary voltage
FAULT
Red
Off Steady
Blink - 2 Hz = Download or startup in progress, not
ready for normal operation, SA Bus devices offline
(such as Netsensors)
Off Steady = No faults
On Steady = Device fault or no application loaded
N2/FC BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal
communication)
Off Steady = No data transmission (auto baud in
progress)
On Steady = Communication lost; waiting to join
communication ring
SA BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal
communication)
Off Steady = No data transmission (N/A - auto baud
not supported)
On Steady = Communication lost; waiting to join
communication ring
EOL
Amber
Off
On Steady = EOL is active
Off Steady = EOL is not active