FS-1300 Combination Fire/Smoke Damper Installation Bulletin 5
5. Wire the actuator as shown in Figure 13. Use
approved high-temperature connections.
To verify operation:
1.
Verify voltage of actuator and power available
before applying power to the actuator.
2.
After power is applied to the actuator, verify that
the damper blades are fully open.
3.
Remove power and verify that the damper blades
fully close.
4.
Apply power and allow the damper blades to
remain in the open position.
5.
Replace and secure the cover to the actuator.
Pneumatic Actuator
1.
Make sure that all linkage fasteners are secure
before making air line connections.
C o pp er
Tu bing
S lee ve
Jacksh aft
U n iversa l M o un tin g B ra cket
Figure 14: Pneumatic Connections
2. Copper tubing must be used and looped to allow
pivoting of the actuator.
!
CAUTION:
Shock Hazard.
Disconnect the electrical power
supply before wiring the
switches and sensor to avoid
possible electrical shock or
damage to the equipment.
3. Make all wiring connections in handy box using
copper conductors and approved solderless
connectors. Wire in accordance with NEC and
local regulations.
To verify operation:
1.
When the air supply is applied to the actuator,
verify that the damper blades are fully open.
2.
Remove the air supply and verify that the damper
blades fully close.
3.
Connect the air supply and allow the damper
blades to remain in the open position.
Table 2: Replacement Parts
Replacement
Code Number
Description
DS-3153-600
Pneumatic Actuator, Body Only
DMPR-RS005
DMPR-S60024 - 60 lb·in, 24 VAC
Actuator
DMPR-RS006
DMPR-S60024S - 60 lb·in, 24 VAC
Actuator w/auxiliary switch
DMPR-RS007
DMPR-S60120 - 60 lb·in, 120 VAC
Actuator
DMPR-RS008
DMPR-S60120S - 60 lb·in, 120 VAC
Actuator w/auxiliary switch
DMPR-RS301
165°F temperature sensor
DMPR-RS302
212°F temperature sensor
DMPR-RS303
250°F fusible link
DMPR-RS304
350°F fusible link