background image

Damper and Actuator Product Guide

268.1

Fire/Smoke Section

Installation Bulletin

FS-1300

Issue Date

0499

© 1999 Johnson Controls, Inc.

1

Part No. 44-352-29, Rev. —

www.johnsoncontrols.com

Code No. LIT-2681195

!

 DANGER: To avoid causing death or

serious bodily harm to building
occupants, follow all instructions
carefully. Dampers must close
completely to preserve the
integrity of the fire barrier.

I

tems Needed

screwdriver, flat-blade

nut driver, 1/2 inch socket

open-end wrench, adjustable to 1 inch

G

eneral

Note:

For further information, refer to
UL File No. R11172 and
CSFM3230-0554:128.

The FS-1300 Combination Fire/Smoke Leakage-rated
Life Safety Damper is designed to restrict the passage
of flame or smoke when in the closed position, under
dynamic or static conditions.

After installation, when power (electric or pneumatic) is
applied to the actuator, the damper blades will be
driven to the open position by the actuator.

When the primary temperature sensor detects heat, it
breaks power to the actuator, closing the damper
blades through the spring-return mechanism of the
actuator. The damper is now in the smoke protection
mode (damper closed via actuator).

If the air temperature reaches the fusible link
temperature (secondary temperature sensor), the link
separates. The damper linkage disengages from the
actuator, allowing the blades to close by a torsion
spring. The damper is now in fire protection mode
(damper closed via torsion spring).

FS-1300 Combination Fire/Smoke Dampers are
approved for mounting in fire walls constructed of
masonry or gypsum wallboard (metal or wood studs)
and in cement floors or ceilings.

Figure 1: Wall Mounting

Figure 2: Floor/Ceiling Mounting

Table 1: Damper Size Limits

Size Limits

Width, in.

Height, in.

Minimum

15

14

Maximum Single Panel

32

48

Damper Maximum

(Wall Installation)

64

96

Damper Maximum

(Floor Installation)

64

72

Note: FS-1300 size limits are a function of past UL tests.

Actual damper size is 1/4 inch less than nominal.

FS-1300 Combination Fire/Smoke Damper Installation

1-1/2 Hour/Class II Leakage

Summary of Contents for FS-1300

Page 1: ...When the primary temperature sensor detects heat it breaks power to the actuator closing the damper blades through the spring return mechanism of the actuator The damper is now in the smoke protection mode damper closed via actuator If the air temperature reaches the fusible link temperature secondary temperature sensor the link separates The damper linkage disengages from the actuator allowing th...

Page 2: ...flow and pressure difference electrical and or pneumatic ratings degradation test temperature intended mounting position Dimensions Airflow 11 16 3 5 4 5 8 5 or 12 5 W idth H eight Figure 3 Mounting Dimensions with Electric Actuator inches 7 Airflow 16 3 5 4 5 8 5 or 12 5 Width Height Figure 4 Mounting Dimensions with Pneumatic Actuator inches Figures 3 and 4 show the typical mounting dimensions f...

Page 3: ...where a duct passes through a required fire barrier The blades when closed shall be within the plane of the fire barrier wall or floor IMPORTANT Horizontal airflow only The damper must be installed in the wall with the fusible link above the centerline of the damper See labels on damper 3 Verify that the fusible link is secure and was not damaged or lost during shipment If the fusible link is miss...

Page 4: ... shall terminate at the sleeve The duct to damper sleeve connection shall be of a breakaway style such as S or double S connectors Use the plain S slip when the duct or sleeve size is slightly different Use the double S slip when the sizes are equal 11 The ducts connecting to the sleeves shall be equal or less than the sleeve thickness All FS 1300 sleeves are 18 gauge galvanized steel Connections ...

Page 5: ...ct the electrical power supply before wiring the switches and sensor to avoid possible electrical shock or damage to the equipment 3 Make all wiring connections in handy box using copper conductors and approved solderless connectors Wire in accordance with NEC and local regulations To verify operation 1 When the air supply is applied to the actuator verify that the damper blades are fully open 2 R...

Page 6: ... x Height in Mounting Ordering Code Maximum Flow fpm Maximum SP in WG Actuator Tested as Matched Set with Damper 350 F Minimum 15 x 14 Wall or Ceiling TOVLP Maximum 32 x 48 Wall TOVHP 2800 8 DS 3153 2 Maximum 32 x 36 Ceiling Note Table 4 information is based on a 20 psi minimum supply pressure for pneumatic actuators Maximum Flow is the velocity against which the actuator listed in Table 4 will be...

Page 7: ...on at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products At Johnson Controls delivering environmentally sound products and services is part of our corporate wide commitment to continuous improvement We do this by reducing raw material consumption recycling elim...

Page 8: ... Combination Fire Smoke Damper Installation Bulletin Notes Controls Group www johnsoncontrols com 507 E Michigan Street FAN 268 1 P O Box 423 Damper and Actuator Product Guide Milwaukee WI 53201 Printed in U S A ...

Reviews: