Accessories
See
Table 9
for controller accessories ordering information.
Table 9: Accessories Ordering Information
Description
Product Code Number
Local Controller Display (for use with MS-FEC2611 model only)
MS-DIS1710-0
Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
TP-2420
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount,
8 in. Primary Leads and Secondary Screw Terminals, Class 2
Note:
Additional Y6x-x Series transformers are also available. Refer to the
Series
Y63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755)
for more
information.
Y65T31-0
Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure
AS-XFR050-0
Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10
AP-TBK4SA-0
Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10
AP-TBK4FC-0
Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack of 10
AP-TBK3PW-0
This system is used for installations that support BACnet/IP but can also coexist
with the ZFR1800 Series when installed under the same supervisor (i.e., network
engine). Refer to the
WNC1800/ZFR182x Pro Series Wireless Field Bus System
Product Bulletin (LIT-12012320)
for a list of available products.
WNC1800/ZRF182x Pro Wireless Field
Bus System
This system is used for installations that only support BACnet MS/TP. Refer to the
ZFR1800 Series Wireless Field Bus System Product Bulletin (LIT-12011336)
for a
list of available products.
ZFR1800 Series Wireless Field Bus
System
Refer to the
NS Series Network Sensors Product Bulletin (LIT-12011574)
for specific
sensor model descriptions.
NS Series Network Sensors
Refer to the
WRZ Series Wireless Room Sensors Product Bulletin (LIT-12000653)
for specific sensor model descriptions.
WRZ Series Wireless Room Sensors
Technical Specifications
Table 10: FEC16 Technical Specifications
MS-FEC1611-1: 10-Point FEC
MS-FEC1611-1ET: FEC1611 Extended Temperature controller for rooftop
applications. Supports operational temperature range of -40 °C to 70 °C (-40 °F to
158 °F).
MS-FEC1621-1: 10-Point FEC with integral display and pushbutton user interface.
Product Code Numbers
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply
Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
Supply Voltage
14 VA maximum for FEC1611 only
20 VA maximum for FEC1621 (with integral display) only
Note:
VA rating does
not
include any power supplied to the peripheral devices
connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can
consume up to 12 VA for each BO or CO; for a possible total consumption of an
additional 84 VA (maximum).
Power Consumption
26
FEC1611 and FEC1621 Field Equipment Controller Installation Instructions