Battery backup (FCP-PA-701 only)
The FCP-PA-701 thermostat includes a lithium coin cell battery to provide battery backup. The
minimum back up time is 48 hours. To activate battery backup, remove the insulation tape under
the coin cell battery. Open the front cover to find the coin cell battery.
Pre-set configuration profiles
You can configure the thermostat in less than 30 seconds with the pre-set configuration profiles.
The thermostat screen shows the preset configuration menu on the first power up or after a factory
reset. Press
Up
or
Down
to select the preferred profile, then press
Mode
to confirm your selection.
The following table lists the pre-set configuration profiles.
Table 2: Pre-set configuration profiles
Profile # Remote
sensor
Pipe
sensor
System
type
2-pipe
FCU with
aux heat
Available
modes:
1: heat
only
2: cool
only
3: heat
and cool
with Auto
4: heat
and cool
without
Auto
HP valve
type
Remote
sensor
location:
0: in
room
1: in duct
Pipe state
- calendar
Pipe
state:
0: heat
1: cool
Number
of fan
speeds
1
No
No
2-pipe FCU No
4
-
0
Off
1
3
2
No
No
2-pipe FCU No
4
-
0
Off
0
3
3
No
Yes
2-pipe FCU No
4
-
0
Off
-
3
4
No
Yes
2-pipe FCU Yes
3
-
0
Off
-
3
5
No
No
2-pipe FCU Yes
3
-
0
Off
1
3
6 (Default) No
No
4-pipe FCU No
4
-
0
Off
-
3
7
Yes
No
2-pipe FCU No
4
-
1
Off
1
3
8
Yes
No
2-pipe FCU No
4
-
1
Off
0
3
9
Yes
Yes
2-pipe FCU No
4
-
1
Off
-
3
10
Yes
Yes
2-pipe FCU Yes
3
-
1
Off
-
3
11
Yes
No
2-pipe FCU Yes
3
-
1
Off
1
3
12
Yes
No
4-pipe FCU No
4
-
1
Off
-
3
13 - 17
Reserved
18
No
No
HP
-
3
O
-
-
-
2
19
No
No
HP
-
3
B
-
-
-
2
20
No
No
H-C
-
3
-
-
-
-
2
Button combinations
The following table describes the button combinations that you can use to access menus or
functions. The table also indicates the modes in which these button combinations are applicable.