Johnson Controls Facility Explorer FX40 Product Bulletin Download Page 7

 

Technical Specifications 

Table 2: FX40 Controller (Part 1 of 2) 

Product Codes 

LP-FX4020A-0, LP-FX4022A-0 

Power Requirements 

120 VAC, 50/60 Hz 

25 VA maximum 

Lead wires for hot/neutral (wire nut), stud for ground connection 

Environmental 

Operating Temperature: 0 to 50

°

C (32 to 122

°

F) 

Storage Temperature: 0 to 70

°

C (32 to 158

°

F) 

Relative Humidity: 5 to 95%, noncondensing 

General 

Motorola® Reduced Instruction Set Computer (RISC) Processor @ 250 MHz  

Facility Explorer Control Engine with direct I/O support objects 

128 MB RAM, 32 MB flash for database backup 

One 10/100 MB Ethernet RJ-45 connector 

FCC Class A computing device 

Wind River VxWorks® Operating System with Jeode® Java® Virtual Machine 

Facility Explorer Software with I/O control objects 

Communications 

One 10/100 Mb Ethernet port–RJ-45 connection 

One RJ-45 connector for RS-232 port 

One RS-485 port (up to 57,600 baud) 

One L

ON

W

ORKS

 port–FTT-10 with Weidmuller connector 

Optional auto-dial/auto-answer 56k modem; RJ-11 connector (uses the RS-
232 port when installed) 

Inputs/Outputs 

Four form C SPDT relay outputs rated for 24 VAC/DC @ 2 ampere resistive 

One LED indicator for each relay 

Six Universal Inputs for 10k ohm Type III (10k 4A1-International) Thermistor, 
4/20 mA current loop, 0 to 10 volt, or dry contact 

12-bit A/D converter 

Thermistor Sensor Range: 23.3 to 57.2

°

C (10 to 135

°

F). Input accuracy is in 

the range of 

±

1% of span, characteristic curve is customizable 

0 – 10 volt or 4/20 mA accuracy is 

±

2% of span, without user calibration. Uses 

an external resistor for current input (four provided). Self-powered or board 
powered sensors accepted. 

Dry contacts (on UI) 20 Hz max. frequency (25 ms minimum pulse width) 3V 
open circuit, 300 µA short-circuit current 

20 VDC @ 80 mA to drive 4/20 mA powered sensors. 

24 VDC terminal and external resistor can be used if monitoring contacts that 
require higher voltages or higher current.  

All I/O uses screw terminals on 0.2 in. centers 

Battery Backup 

Provided for all on board functions including I/O. 

Monitored and trickle charged. 

Battery maintains processor operation through power failures for a 
predetermined interval, then writes all data to flash memory, shuts processor 
down, and maintains clock for a minimum of 5 years. 

FX40 Supervisory Controller Product Bulletin    

7

 

Summary of Contents for Facility Explorer FX40

Page 1: ... alarms The FX40 provides a user interface and configuration tool that users can access with a Web browser Multiple users can concurrently connect to the FX40 Security and presentation preferences are managed through user profiles logon IDs and passwords Remote access is easily achieved from an Internet intranet or a dial up connection Figure 1 FX40 Features and Benefits Web Based User Interface R...

Page 2: ...VDC active inputs or dry contact binary inputs Supported Field Controllers The FX40 can interface with many different types of field controllers and monitoring devices Three field level network communication protocols are currently supported N2 LONWORKS and BACnet IP Ethernet N2 Communication The FX40 includes one RS 485 communication port and an N2 protocol driver that allows integration of a wid...

Page 3: ...jects and services To determine if a third party BACnet device is supported compare its Protocol Implementation Conformance Statement PICS with the FX40 PICS This includes the supported BACnet Interoperability Building Blocks BIBB and details the level of BACnet conformance Figure 2 displays an example of an FX40 configuration Figure 2 Example of an FX40 Configuration FX40 Supervisory Controller P...

Page 4: ...ser Interface UI provides the user with system wide monitoring and controlling capability The UI is embedded and provided by the FX40 This allows users to access the system from anywhere on the supervisory network via a Web browser System administrators can format the UI according to specific user preferences The presentation of the information can be as rich or as limited as needed to support a v...

Page 5: ...larm class The alarm class allows the routing of alarms with similar characteristics to common recipients Users can create multiple alarm classes to have a variety of alarm routing options Users can configure alarm recipients to receive alarms via a Web browser or e mail Alarm recipients have a variety of options to manage alarms including sorting acknowledging silencing and tagging Figure 6 Alarm...

Page 6: ...Supports a maximum of 100 devices Includes a 1 year software maintenance agreement LP FX40MA 0 One additional year of annual software maintenance for one FX40 Includes new releases and interim service releases for 1 year from the date of purchase Covers all applications or drivers licensed for the FX40 LP FX40UPG 0 One time new release software upgrade for one FX40 Includes all applications and dr...

Page 7: ...s Four form C SPDT relay outputs rated for 24 VAC DC 2 ampere resistive One LED indicator for each relay Six Universal Inputs for 10k ohm Type III 10k 4A1 International Thermistor 4 20 mA current loop 0 to 10 volt or dry contact 12 bit A D converter Thermistor Sensor Range 23 3 to 57 2 C 10 to 135 F Input accuracy is in the range of 1 of span characteristic curve is customizable 0 10 volt or 4 20 ...

Page 8: ...ations contact a Facility Explorer technical support resource Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products Federal Communications Commission FCC Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable prot...