background image

Figure  11: End-of-Line switch positions

To set the EOL switch on a field controller, complete the

following steps:

1.

Determine the physical location of the controller on

the FC bus.

2.

Determine if the controller must be set as a

terminating device on the bus.

Note: 

For detailed information regarding EOL

termination rules and EOL switch settings on FC

buses, refer to the 

MS/TP Communications Bus

Technical Bulletin (LIT-12011034)

.

3.

If the controller is a terminating device on the FC

bus, set the EOL switch to ON. If the controller is not

a terminating device on the bus, set the EOL switch

to Off.

When a controller is connected to power with its EOL

switch set to ON, the amber EOL LED on the controller

cover is lit.

Setting the Input Jumpers

 CAUTION

Risk of Electric Shock:

Disconnect supply power to the controller before at-

tempting to adjust the Binary Output Source Power

Selection Jumpers. Failure to disconnect the supply

power may result in electric shock.

 ATTENTION

Risque de décharge électrique

Débrancher l'alimentation de l'controller avant tout

réglage du Binary Output Source Power Selection

Jumpers. Le non-respect de cette précaution risque

de provoquer une décharge électrique.

UI current loop jumpers

The UI current loop fail-safe jumper pins are located on

the circuit board under the controller cover near the UI

terminals.

Note: 

Current Loop Jumpers

 are not included

 with

the MS-FAC3611-0A. (Asia only model.)

Figure  12: Current loop jumper positions

Set the current loop jumper to the Enabled position

(Figure 12) to connect an internal 100 ohms resistor

across the UI terminals, which maintains the 4–20 mA

current loop circuit even when power to the controller is

interrupted or off.

Important: 

Current loop jumpers must be in the

Disabled (default) position for all UIs that are not set

up to operate as 4–20 mA analog inputs.

The following table identifies the current loop switches

associated with each UI on the controller.

Table  7: FAC3611 UI Inputs and jumper labels

Universal Input label

Jumper label on circuit board

IN1

J5

IN2

J6

IN3

J7

IN4

J8

IN5

J9

IN6

J10

IN7

J11

IN8

J12

Commissioning Field Controllers

You commission BACnet MS/TP field controllers with

the (Controller Configuration Tool ) CCT software.

The controller can be connected using NxE Passthru,

Bluetooth (using BTCVT), or through MAP 4.2+/BACnet

Router (Mobile Access Portal (MAP) Gateway at version 4.2

or above). Refer to 

Controller Tool Help (LIT-12011147)

 for

detailed information on commissioning field controllers. .

Note: 

The MAP Gateway serves as a replacement for

the BTCVT, which is no longer available for purchase,

but continues to be supported.

FAC3611 Advanced Application Controller Installation Guide

17

Summary of Contents for FAC3611

Page 1: ...eiver most models are available in Buy American versions most models The N2 capable controllers do not support Zone Bus for example TMZ sensors and M100 actuators or XT Bus System 91 devices for example XT XTM and XP modules do not support a wireless connection to the N2 bus do not support NxE passthrough Fast persistence The FAC3611 model has been significantly upgraded and now includes a fast pe...

Page 2: ...Binary Outputs BO Terminal Block 24 VAC Triac see Table 2 4 24 VAC Class 2 SELV Supply Power Terminal Block see Supply power terminal block 5 Cover Lift Tab One of Two 6 FC Bus Terminal Block see FC bus terminal block 7 SA Bus Terminal Block see SA bus terminal block 8 Sensor Port SA Bus RJ 12 6 Pin Modular Jack see SA Bus port 9 Binary Input BI Terminal Block Dry Contact Maintained or Pulse Count...

Page 3: ... in or longer section of 35 mm DIN rail horizontally and centered in the desired space 2 Pull the two bottom mounting clips outward from the controller to the extended position Figure 3 3 Hang the controller on the DIN rail by the hooks at the top of the DIN rail channel on the back of the controller Figure 3 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips ...

Page 4: ...SA bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 Terminal blocks and bus ports See FAC3611 physical features for terminal block and bus port locations on the FAC3611 controller Observe the following guidelines when wiring a controller Input and Output terminal blocks The fixed input terminal blocks are located on the bottom of the controller and the output terminal bloc...

Page 5: ...n FEC models without integral display and push buttons The Sensor port is connected internally to the SA bus terminal block For more information about the Sensor port functions requirements and ratings see The Sensor Port pin assignment is shown in Figure 6 but only on FEC models without integral display and push buttons Supply power terminal block The 24 VAC supply power terminal block is a gray ...

Page 6: ...e size and maximum cable length 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal INn terminals Provides 100 mA total current Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal Analog Input Voltage Mode 0 10 VDC 10 VDC maximum input voltage Internal 75k ohms pull down See Guideline A in Table 3 Analog Input Current Mode...

Page 7: ...ed to devices with impedances less than 300 ohms Devices that exceed below 300 ohms may not operate as intended for Current Mode applications ANALOG Outputs OCOMn Analog Output Signal Common for all Analog OUT terminals Note All Analog Output Common terminals OCOMn share a common which is isolated from all other commons One common screw terminal point is provided for every two output screw termina...

Page 8: ...puts and Outputs by current and wire size Communications bus and supply power wiring guidelines The provides information about the functions ratings and requirements for the communication bus and supply power terminals The table also provides guidelines for wire sizes cable types and cable lengths for when you wire the controller s communication buses and supply power In addition observe these gui...

Page 9: ...R 15 VDC Supply Power for Devices on the SA Bus Maximum total current draw for SA Bus is 240 mA 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended Note The and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires Sensor Port SENSOR RJ 12 6 Position Modular Connector provides SA Bus Communications SA Bus Signal Reference and 15 VDC Common 15 VD...

Page 10: ... the figures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI FAC3611 Advanced Application Controller Installation Guide 10 ...

Page 11: ...Termination diagrams Current Input External Source Isolated UI Current Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI FAC3611 Advanced Application Controller Installation Guide 11 ...

Page 12: ...grams Dry Contact Binary Input UI or BI 0 10 VDC Output to Actuator External Source CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO Current Output CO or AO 24 VAC Triac Output Switch Low External Source CO or AO FAC3611 Advanced Application Controller Installation Guide 12 ...

Page 13: ...tion diagrams Analog Output Current AO 4 20 mA Output to Actuator AO 4 20 mA Output to Actuator AO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output Switch Low Externally Sourced BO FAC3611 Advanced Application Controller Installation Guide 13 ...

Page 14: ...BO Incremental Control to Actuator Switch High Externally Sourced BO Network Stat with Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus FAC3611 Advanced Application Controller Installation Guide 14 ...

Page 15: ...ugh 1 to OFF 2 Set one or more of the seven address switches 64 though 1 to ON so that the sum of the switch numbers set to ON equals the intended device address and ensure that switch 128 remains set to OFF Note To do this set the highest number switch that is less than or equal to the intended device address to ON Then continue setting lower numbered switches until the total equals the intended ...

Page 16: ... VAC supply to the controller Removing the Controller cover Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller Important Disconnect all power sources to the controller before you remove the cover and change the position of any jumper or the EOL switch on the contr...

Page 17: ...fe jumper pins are located on the circuit board under the controller cover near the UI terminals Note Current Loop Jumpers are not included with the MS FAC3611 0A Asia only model Figure 12 Current loop jumper positions Set the current loop jumper to the Enabled position Figure 12 to connect an internal 100 ohms resistor across the UI terminals which maintains the 4 20 mA current loop circuit even ...

Page 18: ... Code download required if controller is in Boot mode Blink 2 Hz Download or Startup in progress not ready for normal operation SA BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady No Data Transmission N A auto baud not supported On Steady Communication lost waiting to join communication ring FC BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication ...

Page 19: ... Primary Leads and Secondary Screw Terminals Class 2 Note Additional Y6x x Series transformers are also available Refer to the Series Y63 Y64 Y65 Y66 and Y69 Transformers Product Bulletin LIT 125755 AS XFR050 0 for more information Power transformer Class 2 24 VAC 50 VA maximum output no enclosure for more information AP TBK4SA 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack of 10 ...

Page 20: ...imum of 72 hours when supply power to the controller is disconnected Input and Output Capabilities 6 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mode 6 Binary Outputs Defined as 24 VAC Triac external power source only 6 Analog Outputs Defined as 0 10 VDC or 4 20 mA Analog Input Analog Output Resolution and Accuracy Input 15 bit resolution Output 15 bit resolution 2...

Page 21: ...roduct is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact ...

Page 22: ...FAC3611 Advanced Application Controller Installation Guide 22 ...

Reviews: