UI Current Loop Jumpers
The current loop fail-safe jumpers are on the circuit board
under the controller cover near the UI terminals (
). When a UI is defined (in the system software) as a
4-20 mA Analog Input and the UI’s current loop jumper
is in the Disabled (default) position (
), the 4-20
mA current loop circuit opens whenever power to the
controller is interrupted or off.
Figure 13: Current Loop Jumper Positions
Setting the current loop jumper to the Enabled position
(
) connects an internal 100 ohm resistor across
the UI terminals, which maintains the 4-20 mA current
loop circuit even when power to the controller is
interrupted or off.
Important:
Current Loop jumpers must be in the
Disabled (default) position for all UIs that
are not set up to operate as 4-20 mA analog
inputs.
identifies the current loop switches associated
with each UI on the FAC2611 controller.
Table 7: FAC2611 UI Inputs and Jumper Labels
Switch Label on Current Loop DIP
Switch Block Board
Universal Input
Label
J20
IN1
J21
IN2
J22
IN3
J23
IN4
J24
IN5
J25
IN6
Commissioning Field Controllers
You commission BACnet
®
MS/TP field controllers with
the Controller Configuration Tool (CCT) software. Refer
to
Controller Tool Help (LIT-12011147)
for detailed
information on commissioning field controllers.