background image

F61 Series Standard Flow Switches Installation Instructions    

3

Mounting

!

 CAUTION: Risk of Equipment Damage.

To avoid damaging the switch, do not tighten the
switch to the tee by grasping the switch enclosure.
Use only the wrench flats provided.

Mount the F61 Series Flow Switch, using the following
guidelines:

  Install the switch so that the cover and interior are

accessible.

  Mount the switch so that the flow of fluid is in the

direction of the arrow on the switch casing.

  Use a pipe union on each side of the flow switch to

allow easy removal or replacement.

  Mount the switch so that the pipe does not extend

too far into the flow switch casing.

  Use pipe thread sealer on male threads only.

  Do not remove the cover gasket or the wire

grommet from the conduit opening.

For 1 in. pipe installation, mount the F61 flow switch in
a standard 1 in. x 1 in. x 1 in. tee. For larger sizes of
pipe, use a reducing tee to keep the flow switch close
to the pipe and provide adequate paddle length in the
flow stream.

Example: Use a 2 in. x 2 in. x 1 in. tee for a
2 in. pipe. If a standard 2 in. x 2 in. x 2 in. tee is
used, install a face or hex bushing in the top
opening to reduce it to 1 in.

Mount the flow switch so the terminals or wire leads
are easily accessible for wiring. Screw the flow switch
in position so the flat of the paddle is at a right angle to
the flow. The arrow on the side of the case must point
in the direction of the flow.

Location Considerations

Mount the F61 flow switch in a horizontal pipeline or a
vertical pipeline with upward fluid flow. Do not use in a
vertical pipeline with downward flow. When mounted in
a vertical pipe with upward flow, the switch trips at a
slightly higher flow than shown in Table 3 through
Table 6

due to the effect of gravity on the switch

mechanism.

Mount the F61 flow switch in a section of pipe where
there is a straight run of at least five pipe diameters on
each side of the flow switch from the nearest elbow,
valve, or other pipe restriction. See Figure 5.

Dimension   must be at least 

five pipe diameters from the nearest

elbow, valve, or other pipe restriction.

A

A

A

Tee or Welded 
Half-coupling

Figure 5: Required Piping Distance

Do not subject the flow switches to water hammer.
Use a suitable water hammer arrester if a fast-closing
valve is located downstream of the flow switch. See
Figure 6.

Flow 

Switch

Water 

Hammer 

Arrester

Valve

Flow

Figure 6: Water Hammer Arrester Location

Schematic

Wiring

!

WARNING: Risk of Electrical Shock.

Disconnect power supply before making electrical
connections. Failure to follow this precaution may
result in electrical shock or death.

!

 CAUTION: Risk of Equipment Damage.

Using terminal screws other than those provided will
void the warranty and may damage the switch. Use
only the terminal screws furnished.

IMPORTANT:

 To prevent moisture from entering

and condensate from forming inside the NEMA 3R
enclosure, do not remove the cover gasket or the
wire grommet from the conduit opening.

Summary of Contents for F61 series

Page 1: ...dard models of the F61 flow switch include an installed three piece flow paddle Some models also include a large flow paddle for large pipe sizes Table 1 Replacement Parts Kit Number Description KIT21A 600 Stainless Steel Three piece Paddle 3 in 2 in and 1 in Segments KIT21A 601 Stainless Steel 6 in Paddle PLT52A 600R Stainless Steel Three piece Paddle 3 in 2 in and 1 in Segments and 6 in Paddle C...

Page 2: ... 1 2 64 1 1 8 29 1 1 8 29 1 1 8 29 1 1 8 29 1 25 2 51 3 76 3 1 2 89 4 101 6 5 8 168 6 5 8 168 5 152 Figure 3 NEMA 1 Enclosure F61KB Types Dimensions in mm 1 in 11 1 2 NPT Use these wrench flats to tighten the flow switch at installation Paddle Screw 2 3 4 71 1 3 8 35 2 7 8 73 1 9 16 40 4 3 4 121 1 1 16 27 B A 1 1 4 33 3 11 16 94 1 13 16 47 1 1 8 29 On MB and MG Types 5 8 15 On LB Types 1 2 14 NPSM...

Page 3: ... case must point in the direction of the flow Location Considerations Mount the F61 flow switch in a horizontal pipeline or a vertical pipeline with upward fluid flow Do not use in a vertical pipeline with downward flow When mounted in a vertical pipe with upward flow the switch trips at a slightly higher flow than shown in Table 3 through Table 6 due to the effect of gravity on the switch mechani...

Page 4: ...roper Operation The switch is factory set at approximately the minimum flow rate see Table 3 through Table 6 Do not set lower than the factory setting because that may result in the switch failing to return to a no flow position CAUTION Risk of Equipment Damage Sealed settings screws marked with black paint are not intended to be changed Adjustment attempts may damage the control or cause loss of ...

Page 5: ... to B Closes 2 50 0 57 3 70 0 84 5 00 1 14 9 50 2 16 12 5 2 84 19 0 4 32 50 0 11 4 101 22 9 158 35 9 320 72 7 Flow Increase R to Y Closes 8 80 2 0 13 3 3 02 19 2 4 36 29 0 6 59 34 5 7 84 53 0 12 0 128 29 1 245 55 6 375 85 2 760 173 Maximum Adjustment Flow Decrease R to B Closes 8 50 1 93 12 5 2 84 18 0 4 09 27 0 6 13 32 0 7 27 50 0 11 4 122 27 7 235 53 4 360 81 8 730 166 1 Values for 2 in paddle t...

Page 6: ...for factory installed set of 1 2 and 3 in paddles Table 6 F61MG Models 6 in Paddles GPM m3 hr Required to Actuate Switch Pipe Size in 4 5 6 8 Flow Increase R to Y Closes 35 0 7 95 53 0 12 0 69 0 15 7 197 44 7 Minimum Adjustment Flow Decrease R to B Closes 27 0 6 13 41 0 9 31 54 0 12 3 170 38 6 Flow Increase R to Y Closes 80 0 18 2 116 26 3 142 32 2 412 93 6 Maximum Adjustment Flow Decrease R to B ...

Page 7: ...witch mechanism Clear any debris within the switch mechanism Test the operation of switch several times for proper operation Control switch action is reversed Ensure connections follow wiring diagrams Control does not switch Check connections Switch fails to return to the no flow position Switch is set lower than the factory setting Increase the setting On vertical pipes ensure that direction of f...

Page 8: ...r 1 2 in Conduit 1 2 14 NPSM Threads F61LB F61MB F61MG UL Listed E5368 CCN NMFT Agency Listings CSA Certified LR948 Class 3211 06 Class 4813 02 Class 1222 01 F61KB F61LB Not CSA Certified LR948 Class 3211 06 F61MB F61MG Shipping Weight 2 8 lb 1 3 kg The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these specifications cons...

Reviews: