WIRING

Furnace wiring is complete except for the power supply and the thermo-
stat wires. See wiring diagrams (Figures 13–18) for wire and fuse size.
See Table 2 for ground wire sizes. Thermostat wires connect through
side of furnace and should also be no smaller than 22 gauge. Power
wires can enter through the side of the unit or through the auxiliary
entrance, located in the bottom of the unit. (See Figure 1). When bring-
ing wiring through the bottom of the furnace, cable connectors must be
installed to hold wiring in place and to relieve any strain on the wiring.
These connectors also serve as a seal between the furnace and the
floor. Thus, additional sealing is not required.

Refer to the National Electrical Code, Canadian Electrical Code and
local codes for wiring material requirements.

Models for EBE/EUE15*, EBE/EUE17*, EBE/EUE20*, and EBE/
EUE23* may be connected to a single or dual branch circuit.

These units are shipped from the factory set up for dual power supply
connections. For single power supply connections, jumper bars (P/N
3500-378P*) are required and are available from the factory. See Fig-
ures 11 and 12.

NOTICE

The furnaces are equipped with either one or two 60 amp circuit
breakers. These circuit breakers protect the wiring inside of the fur-
nace in the event of a short circuit. Additionally, these breakers pro-
vide a means of disconnecting the power to the unit. The circuit
breakers in the furnace are not meant to protect the branch circuit
wiring between the furnace and the home's breaker panel. General
wire and breaker sizes are shown in Table 2. If sheathed cable is
used, refer to National Electrical Code, Canadian Electrical Code
and local codes for additional requirements concerning supply cir-
cuit wiring. Electrical Data can be found in Table 4.

IMPORTANT

All installation on field wiring must be rated at 60ºC or higher.

TABLE 2: 

Wiring Requirements

MODELS

1

EBE10A

EUE10A

1. Does Not require a Jumper.

2

EBE12A

EUE12A

2. Jumper provided for Single Branch Circuit Only.

3

EBE15A

EUE15A

3. Requires Jumper Bars (P/N 3500-378P).

3

EBE17A

EUE17A

3

EBE20A

EUE20A

3

EBE23A

EUE23A

Single Branch Circuit Service

2 Leads + 1 Ground CKT #1

Nominal Circuit Load - Amps

43.8

50.5

63.8

70.4

83.8

93.8

Minimum Wire Size (90ºC)

#8

#6

#4

#4

#3

#2

Minimum Wire Size (75ºC)

#6

#6

#4

#3

#2

#1

Minimum Wire Size (60ºC)

#6

#4

#3

#2

#1

#0

Ground Wire Size +

#10

#8

#8

#8

#6

#6

Max. Fuse (or C.B.) - Amps

60

70

80

90

110

125

Dual Branch Circuit Service

NOT

APPROVED

CKT #1

CKT #2

CKT #1

CKT #2

CKT #1

CKT #2

CKT #1

CKT #2

Branch Circuit Load - Amps

43.8

20.0

47.1

23.3

43.8

40.0

47.1

46.7

Branch Circuit Min. - Amps

54.8

25.0

58.9

29.1

54.8

50.0

58.9

58.4

Minimum Wire Size (90ºC)

#8

#10

#6

#10

#8

#8

#6

#6

Minimum Wire Size (75ºC)

#6

#10

#6

#10

#6

#8

#6

#6

Minimum Wire Size (60ºC)

#6

#10

#4

#10

#6

#6

#4

#4

Ground Wire Size 

4

4. Refer to National Electrical Code (NEC). Table 250-122 for Non-Sheathed Conductor Ground Wire.

#10

#10

#10

#10

#10

#10

#10

#10

Max. Fuse (or C.B.) - Amps

60

30

60

30

60

50

60

60

NOTES: 

TABLE 3: 

EBE/EUE Series Blower Performance

Static Pressure 
(inches of w.c.)

Speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM (STD. Air) 

for all EBE/EUE Models

Hi

1607

1563

1515

1477

1434

1406

1377

1345

MH

1390

1346

1298

1286

1253

1224

1201

1160

M

1241

1192

1151

1115

1097

1074

1032

1000

ML

1099

1051

1002

979

949

912

872

855

Lo

1006

950

923

896

860

826

800

728

Summary of Contents for EBE Series

Page 1: ...furnace and its packaging inclusions 1 Furnace is rated at 240 volts 60 Hz single phase 2 Filters are furnished with EBE model and are the same for all EBE models 16 x 20 x 1 in top and 20 x 20 x 1 i...

Page 2: ...8 Installing and servicing heating cooling equipment can be hazard ous due to the electrical components Only trained and qualified personnel should install repair or service heating cooling equip ment...

Page 3: ...led below furnace The return air opening can be located in a closet front door or a side wall above the furnace casing or in a louvered door on the furnace If opening for the return air is located in...

Page 4: ...rnace to an under the floor supply duct system The furnace may be installed on combustible flooring without a separate sub base TABLE 1 Duct Connector for Electric Furnaces FLOOR TO DUCT DIMENSIONS FI...

Page 5: ...ough and back up under the supply duct 8 Secure the duct connector to the floor with nails flat head screws or staples The duct connector is designed for use on ducts down to 12 in width When using th...

Page 6: ...reaker panel General wire and breaker sizes are shown in Table 2 If sheathed cable is used refer to National Electrical Code Canadian Electrical Code and local codes for additional requirements concer...

Page 7: ...other applicable codes 2 Does Not require a Jumper 3 Approved for Single Branch Circuit Service Only 4 Jumper provided for Single Branch Circuit Only 5 Requires Jumper Bars P N 3500 378P WARNING For p...

Page 8: ...n 19 1 2 no wider than 18 1 4 and no deeper than 20 1 2 EUE Furnace Models No extension cabinet and coil shelf are needed for the EUE upflow fur nace The coil shelf is already installed in the EUE mod...

Page 9: ...OCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395383 UWD B 1017 LINE LOAD XFMR 3A FUSE RE...

Page 10: ...ER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395384 UWD B 1017 LINE LOAD XFMR 3A FUSE RED 8 RED 9 Y G W HEAT COOL...

Page 11: ...ED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395385 UWD B 1017 60 AMP CIRCUIT 1 BREAKER 60 AMP 240 VAC 60Hz 1 PHASE CIRCUIT 2 BREAKER GND LUG SINGLE BRANCH CIRCUIT SERVICE 240 VAC 60 Hz 1 PHASE REQUIRES...

Page 12: ...OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE W...

Page 13: ...REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395388 UWD A 0717 LINE LOAD XFMR 3A FUSE RED 8 RED 9 Y G W HEAT COOL T STAT BLK 1 M3 M1 M2 H2 M5 M6 H4 H3 WHT BLK S...

Page 14: ...CH CIRCUIT SERVICE GND ECM ELECTRIC FURNACE 23kW CONDENSING UNIT CONTACTOR 240 VAC 60 Hz 1 PHASE REQUIRES JUMPER BARS P N 3500 378 YEL 13 WHT 11 M4 H1 RED SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO...

Reviews: