1) R-410A refrigerant oil is applied to entire
diaphragm surface, o-ring, and threaded male
coupling end.
2) Coupling halves must be held in proper
alignment with each other prior to starting the
threads of the female coupling nut onto the
male half. Thread by hand the first 3 rotations
of the union nut. If nut does not start by hand,
adjust position of the line set or if necessary
position of unit module.
3) Using a back-up wrench tighten the female
union nut until a definite increase in resistance
is felt. At this point most of threads will have
been covered by the nut. Ensure that the
female and male bodies during any portion of
the wrench installation do not rotate.
4) Make note of the location of the female nut to
the bulkhead. Using a marker or scribe to mark
a line lengthwise. Then finally tighten an
additional one wrench flat or 60
o
. This final
tightening is necessary to ensure a proper leak
proof seal between the couplings.
Summary of Contents for DSH Series
Page 4: ...FORM 145 32 IOM4 818 4 ...
Page 5: ...FORM 145 32 IOM4 818 5 DSH024C DSH060C SINGLE COMPRESSOR UNIT TYPICAL INSTALLATION DIAGRAM ...
Page 6: ...FORM 145 32 IOM4 818 6 DSH096B 120B DUAL COMPRESSOR UNIT TYPICAL INSTALLATION DIAGRAM ...
Page 7: ...FORM 145 32 IOM4 818 7 NOMENCLATURE TABLE ...
Page 18: ...FORM 145 32 IOM4 818 18 UNIT CORNER WEIGHTS ...
Page 21: ...FORM 145 32 IOM4 818 21 TYPICAL WIRING SCHEMATICS ...
Page 22: ...FORM 145 32 IOM4 818 22 ...