Table 2: DSH/DSV/CSV only factory parameters for multi-speed evaporator application -
208/230V and 460 VAC (ABB ACS320)
Name
Value
Unit
99
Start-up data
01
Language
English
02
Applic macro
HVAC default
05
Motor nom volt
Drive dependent
V
06
Motor nom curr
Drive dependent
A
07
Motor nom freq
60
Hz
08
Motor nom speed
Drive dependent
rpm
09
Motor nom power
Drive dependent
hp
10
Start/stop/dir
01
Ext1 commands
DI1
02
Ext2 commands
DI1
11
Reference select
01
Keypad ref sel
Ref1 (Hz/rpm)
02
Ext1/ext2 sel
Ext2
03
Ref1 select
KEYPAD
04
Ref1 min
0
Hz
05
Ref1 max
60
Hz
06
Ref2 select
AI1
07
Ref2 min
0
08
Ref2 max
100
13
Analogue inputs
01
Minimum AI1
20
%
02
Maximum AI1
100
%
14
Relay outputs
01
Relay output 1
FLT/alarm
16
System controls
01
Run enable
DI1
08
Start enable 1
Not sel
09
Start enable 2
Not sel
20
Limits
03
Max current
Drive dependent
A
07
Minimum freq
30
Hz
08
Maximum freq
60
Hz
34
Panel display
01
Signal1 param
Output freq
02
Signal1 min
0
Hz
03
Signal1 max
60
Hz
04
Output1 DSP form
+0.0
05
Output1 unit
Hz
06
Output1 min
0
07
Output1 max
60
08
Signal2 param
Current
09
Signal2 min A
0
VFD for D-Series (DSV/DSH) Air-cooled Self-Contained Units, and C-Series (CSV) Water-Cooled Self-Contained Units,
C-Gen
18
Johnson Controls