Johnson Controls CD-P Series Installation Manual Download Page 3

Figure 5: Transmitter PCB

Configuring the Output

About this task:

The transmitter is capable of generating either voltage or

current output. To select, refer to Figure 5 and:

1. Connect the common wire to Terminal 0.
2. Connect the other wire to:

- Terminal V (for voltage output)

- Terminal mA (for current output) and

configure the pins marked 0/4mA as follows:

- - 4 to 20 mA: connect the jumper so

that it shorts the pins (default)

- - 0 to 20 mA: disconnect (do not

discard) the jumper

3. If the unit has an optional relay accessory, follow

the procedure described in the 

Wiring the Relay

section and then reposition the cover.

Wiring the Relay

Model CD-PR0-00-0 is shipped with a relay module. To wire

the relay, see Figure 6, and attach the relay wires to the

relay PCB's two screw terminals.

Figure 6: Relay PCB

The relay has two setpoint values: the On level and the Off

level. These levels provide hysteresis and desired control

function. The On level must be higher than the Off level.

When CO

2

 concentration is increasing; the relay closes at

the On level, and the relay opens when concentration is

reduced to the Off level.

Note: 

The default relay setpoints are 1,000 ppm On

and 950 ppm Off. Change these settings by entering

new values using the Relay Setpoint Software ACC CD

S.

Setup and Adjustments

Commissioning

Johnson Controls® Carbon Dioxide (CO

2

) transmitters

come from the factory calibrated for the following:
• output signal (0 to 10 V) proportional to CO

2

concentration (0 to 2,000 parts per million [ppm])

• altitude range of 0 to 1,969 ft (0 to 600 m) above sea

level without compensation

• default relay output trigger point of 1,000 ppm

Altitude Compensation

The sensors are calibrated for an altitude of 984 ft (300

m) above sea level and are intended for applications

within the range of 0 to 1,969 ft (0 to 600 m) without

compensation.
For altitudes above 1,969 ft (600 m) where optimum

accuracy of the CO

2

 concentration measurement is

essential, modify the Building Automation System (BAS)

controller’s Analog Input (AI) high range to compensate

for sensor placement at other than the standard

calibration altitude.

Note: 

For altitude compensation, only adjust the AI

high range. The AI low range should remain at zero.

To modify the controller’s AI, reset the 2,000 ppm value

using the controller's Compensation Factor (CF) shown in

Figure 7 or Figure 8 as follows:
Corrected Value = CF x 2,000
For example, if the sensor is situated at an altitude of 3,000

ft (914.4 m) above sea level, CF, from either Figure 7 or

Figure 8, is 1.10.
The new value is calculated as follows:
Corrected Value = (1.10)(2,000 ppm) = 2,200 ppm

Figure 7: Altitude Compensation in Feet Above Sea

Level

CD-Pxx-00-0 Series Duct Mount CO

Transmitter Installation Guide

3

Reviews: