Johnson Controls BUQ024 Installation Manual Download Page 1

R-410A

      

         

BUQ024-060

          

2-5 Ton

527929-BIM-F-0911

ISO 9001

Certified Quality

Management System

TABLE OF CONTENTS

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   3

Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   3
Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   4
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   4
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   7
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   7
Filters  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   7
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   8
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   8
Thermostat  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   8
Power And Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . .   8

Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   12
Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   12

Airflow Performance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   13

Blower Speed Selection  . . . . . . . . . . . . . . . . . . . . . . . . . .   20

Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   21

Cooling Sequence Of Operations . . . . . . . . . . . . . . . . . . .   21
Heating Sequence Of Operations . . . . . . . . . . . . . . . . . . .   21

Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   25

Normal Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   25

Troubleshooting  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   25

Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   26

LIST OF TABLES

1 Unit Limitations  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    3
2 Unit Accessory Weights  . . . . . . . . . . . . . . . . . . . . . . . . . .    5
3 Unit Dimensions Front . . . . . . . . . . . . . . . . . . . . . . . . . . . .    5
4 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    5
5 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    10
6 Physical Data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    11
7 Side Duct Application  . . . . . . . . . . . . . . . . . . . . . . . . . . .    13
8 Bottom Duct Application  . . . . . . . . . . . . . . . . . . . . . . . . .    16

9 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . .    19

10 Electric Heat Minimum Supply Air  . . . . . . . . . . . . . . . . .    20
11 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . .    20
12 Electric Heat Multipliers  . . . . . . . . . . . . . . . . . . . . . . . . .    20
13 Delay Profile  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    21
14 Thermostat Signals (Single Phase Units) . . . . . . . . . . . .    23
15 Thermostat Signals (Three Phase Units)  . . . . . . . . . . . .    24

LIST OF FIGURES

1 Component Location  . . . . . . . . . . . . . . . . . . . . . . . . . . . .   3
2 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . .   4
3 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   5
4 Dimensions Front and Bottom . . . . . . . . . . . . . . . . . . . . .   6
5 Dimensions Back and Bottom  . . . . . . . . . . . . . . . . . . . . .   6
6 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   7

7 Typical Field Control Wiring Diagram  . . . . . . . . . . . . . . .    9
8 Field Power Wiring Diagram  . . . . . . . . . . . . . . . . . . . . . .    9
9 Control Board Speed Tap Location  . . . . . . . . . . . . . . . .    21

10 Demand Defrost “Curve” Selection Jumper . . . . . . . . . .    22
11 R-410A Quick Reference Guide  . . . . . . . . . . . . . . . . . .    29

General

Unitary Products Model BUQ units are factory assembled heat 
pumps designed for outdoor installation on a roof top or a slab. 
Field-installed electric heater accessories are available to 
provide supplemental electric heat combined with electric 
cooling and heating.

The units are completely assembled on rigid, removable base 
rails. All piping, refrigerant charge, and electrical wiring is 
factory installed and tested. The units require only electric 
power and duct connections at the point of installation.

The electric heaters have nickel-chrome resistance wire 
elements and utilize single point power connection.

Safety Considerations

This is a safety alert symbol  . When you see this symbol on 
labels or in manuals, be alert to the potential for personal injury.

Understand and pay particular attention the signal words 

DANGER

WARNING

 or 

CAUTION

.

DANGER

 indicates an 

imminently

 hazardous situation, which, 

if not avoided, 

will result in death or serious injury.

WARNING

 indicates a 

potentially

 hazardous situation, which, 

if not avoided, 

could result in death or serious injury.

CAUTION

 indicates a potentially hazardous situation, which, if 

not avoided 

may result in minor or moderate injury.

 It is also 

used to alert against unsafe practices and hazards involving 
only property damage.

Improper installation may create a condition where the 
operation of the product could cause personal injury or 
property damage. Improper installation, adjustment, 
alteration, service or maintenance can cause injury or 
property damage. Refer to this manual for assistance or 
for additional information, consult a qualified contractor, 
installer or service agency.

Summary of Contents for BUQ024

Page 1: ...y assembled heat pumps designed for outdoor installation on a roof top or a slab Field installed electric heater accessories are available to provide supplemental electric heat combined with electric...

Page 2: ...to building electrical and mechanical codes Before performing service or maintenance operations on unit turn off main power switch to unit Electrical shock could cause personal injury Improper install...

Page 3: ...ondenser Fan Motor Highly Efficient Enhanced Copper Tube Aluminum Fin Indoor Coil Highly Efficient Enhanced Copper Tube Aluminum Fin Outdoor Coil Decorative Protective Coil Guard ECM Direct Drive Blow...

Page 4: ...the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars whose length exceeds the largest dimension across the unit MUST...

Page 5: ...SIDE RETURN AIR OPENING SIDE SUPPLY AIR OPENING LOW VOLTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 1 31 32 DIA KNOCKOUT HIGH VOLTAGE CONN 7 8 DIA KNOCKOUT A 3 3 4 1 1 2 2 1 2 2 3 8 4 1 2 49 1 8 28 1...

Page 6: ...T 26 3 4 CONDENSATE DRAIN 3 4 NPTF LOW VOLTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 1 31 32 x 7 8 KNOCKOUT 22 1 2 43 1 2 40 1 2 4 14 1 2 28 3 8 14 1 2 BACK 3 3 8 SIDE RETURN AIR OPENING 14 1 2 4 1...

Page 7: ...bottom supply and return air duct openings Roof Curb On applications when a roof curb is used the unit must be positioned on the curb so the front of the unit is tight against the curb Filters Single...

Page 8: ...and or local ordinances The unit must be electrically grounded in accordance with local codes or in their absence with the N E C C E C Voltage tolerances which must be maintained at the compressor te...

Page 9: ...or all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY THERMOSTAT CFM CONTROL BOARD TERMINAL STRIP 24 VOLT TRANSFORMER NOTE HEAT ANTICI...

Page 10: ...NE04501006 7 5 10 2 36 1 41 7 45 1 52 1 50 60 2NE04501506 11 3 15 2 54 2 62 5 67 7 78 1 70 80 208 230 3 60 10 4 73 16 2 6 6 8 None 22 4 30 2NH04501025 7 5 10 1 20 8 24 1 48 5 52 5 50 60 2NH04501525 11...

Page 11: ...4 47 4 54 5 ARI net capacity Mbh 23 28 6 35 2 42 46 5 54 0 EER 12 0 12 0 12 0 12 0 12 0 12 0 SEER 14 0 14 0 14 0 14 0 14 0 14 0 Nominal CFM 800 1050 1100 1400 1400 1500 System power KW 1 9 2 4 2 9 3...

Page 12: ...p Prop Prop Prop Drive type Direct Direct Direct Direct Direct Direct Quantity of motors 1 1 1 1 1 1 Motor HP each 1 3 1 3 1 3 1 3 1 3 1 2 No speeds 1 1 1 1 1 1 RPM 1100 1100 1100 1100 1100 1100 Nomin...

Page 13: ...880 121 140 160 181 Y1 W1 COOL C HEAT D 900 127 146 167 188 Y1 W1 COOL D HEAT A 800 99 118 137 157 Y1 W1 COOL D HEAT B 720 80 98 117 135 Y1 W1 COOL D HEAT C 880 121 140 160 181 Y1 W1 COOL D HEAT D 90...

Page 14: ...High Y1 O COOL A 1400 350 398 445 491 535 579 624 670 714 Y1 O COOL B 1300 301 347 392 437 479 522 568 616 662 Y1 O COOL C 1500 399 449 498 546 591 636 680 725 767 Y1 O COOL D 1600 448 500 551 600 647...

Page 15: ...48 060 5 0 Cool High Y1 O COOL A 1500 387 420 453 487 520 554 587 621 654 Y1 O COOL B 1600 486 520 553 587 620 654 687 721 754 Y1 O COOL C 1800 667 700 733 766 800 833 867 900 934 Y1 O COOL D 2000 857...

Page 16: ...140 160 181 Y1 W1 COOL C HEAT D 900 127 146 167 188 Y1 W1 COOL D HEAT A 800 99 118 137 157 Y1 W1 COOL D HEAT B 720 80 98 117 135 Y1 W1 COOL D HEAT C 880 121 140 160 181 Y1 W1 COOL D HEAT D 900 127 146...

Page 17: ...igh Y1 O COOL A 1400 350 398 445 491 535 579 624 670 714 Y1 O COOL B 1300 301 347 392 437 479 522 568 616 662 Y1 O COOL C 1500 399 449 498 546 591 636 680 725 767 Y1 O COOL D 1600 448 500 551 600 647...

Page 18: ...8 060 5 0 Cool High Y1 O COOL A 1500 387 420 453 487 520 554 587 621 654 Y1 O COOL B 1600 486 520 553 587 620 654 687 721 754 Y1 O COOL C 1800 667 700 733 766 800 833 867 900 934 Y1 O COOL D 2000 857...

Page 19: ...0 700 0 01 0 00 0 02 0 03 800 0 01 0 01 0 02 0 03 900 0 01 0 01 0 02 0 04 1000 0 02 0 01 0 02 0 04 1100 0 03 0 01 0 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08...

Page 20: ...ashes once for every 100 CFM i e 12 flashes 1200 CFM Table 10 Electric Heat Minimum Supply Air Size Tons Voltage Minimum Supply Air CFM Heater kW 3 8 5 0 5 6 7 5 7 5 10 0 11 3 15 0 15 0 20 0 18 8 25 0...

Page 21: ...supplied to the compressor and outdoor fan motor and the reversing valve switches to the cooling position When the fan switch on the thermostat is in the AUTO position the indoor blower motor is ener...

Page 22: ...e unit is so equipped For trouble shooting purposes the defrost cycle can be manually initiated by shorting the TEST pins together for 5 seconds Defrost will terminate normally during the TEST mode De...

Page 23: ...ON HEATER BANK 2 ELEC HEAT 10 SEC DELAY ON HEATER BANK 3 ELEC HEAT 20 SEC DELAY ON OFF HEATER BANK 3 ELEC HEAT INSTANT OFF HEATER BANK 2 ELEC HEAT 1 2 SEC DELAY OFF HEATER BANK 1 ELEC HEAT 1 SEC DELA...

Page 24: ...ELAY DETERMINED BY DELAY JUMPER SETTING G W ON BLOWER INSTANT ON HEATER BANK 1 2 3 ELEC HEAT INSTANT ON HEATER BANK 4 5 6 ELEC HEAT 10 SEC DELAY ON OFF HEATER BANK 4 5 6 ELEC HEAT INSTANT OFF HEATER B...

Page 25: ...suitable means If water is used to clean the coil be sure that the power to the unit is shut off prior to cleaning Troubleshooting Prior to any of the following maintenance procedures shut off all po...

Page 26: ...527929 BIM F 0911 26 Johnson Controls Unitary Products Wiring Diagrams Typical BUQ024 060 Heat Pump 208 230 1 60 volt Wiring Diagram...

Page 27: ...527929 BIM F 0911 Johnson Controls Unitary Products 27 Typical BUQ030 060 Heat Pump 230 3 60 volt Wiring Diagram...

Page 28: ...527929 BIM F 0911 28 Johnson Controls Unitary Products Typical BUQ030 060 Heat Pump 460 3 60 volt Wiring Diagram...

Page 29: ...arging cylinders and recovery equipment must be dedicated for use on R 410A systems only Manifold sets must be at least 700 psig high side and 180 psig low side with 550 psig retard All hoses must hav...

Reviews: