![Johnson Controls Autocall MX Indoor Isolated Callpoint Quick Start Manual Download Page 2](http://html1.mh-extra.com/html/johnson-controls/autocall-mx-indoor-isolated-callpoint/autocall-mx-indoor-isolated-callpoint_quick-start-manual_2023551002.webp)
Operation
Reading the LED status
Table 4: LED status
Status
LED
Normal
LED OFF
Short circuit
LED ON - YELLOW
Activated
LED ON - RED
Activating the callpoint
Press the large dot. A spring pushes the plastic element downwards, this
closes a switch and triggers a signal to the control panel.
Testing the callpoint
1. Insert the test/reset key into the slot in the bottom of the unit and pull
the sliding plate downwards.
Note:
This may cause an alarm.
2. Remove the key. The deformable element facilitates testing by activating
the callpoint as normal. This is non-destructive.
Resetting the callpoint
1. Insert the test/reset key into the slot in the bottom of the unit and pull
the sliding plate downwards. The element can now snap back to its non-
deformed state.
2. To close the callpoint, push the sliding plate upwards until it snaps into
Replacing the glass of deformable element
1. Insert the test/reset key into the slot in the bottom of the unit and pull
the sliding plate down until it seperates from the unit.
2. Remove the deformable element, pulling away the bottom first. Fit the
replacement then push the sliding plate upwards until it snaps back into
place.
Figure 3: Resetting the callpoint
Specifications
Table 5: Specifications
Specification
Rating
System compatibility
Compatible with Simplex 4100ES and 4010ES
Environment
Indoor applications only
Operating temperature
-10°C to +55°C
Storage temperature
-30°C to +70°C
Material
Flame retardant ABS
Operating humidity
Up to 90% non-condensing
Dimensions (H x W x D)
93 mm x 89 mm x 27.5 mm
(3.7 in. x 3.5 in. x 1.1 in.)
Weight
110 g (3.9 oz.)
Mounting
Surface or flush
Standby current @ 40 VDC
0.3 mA
Alarm current @ 40 VDC
2.456 mA